Configuring with Turck Safety Configurator and Rockwell Studio 5000
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
62
Switch-off of FDX4/5 if emergency shutdown or light grid activated
Output FDX4/5 at C2 (3. has to be switched off as soon as the emergency shutdown
at FDI0/1 (64. OSSD) or the light grid at FDI2/3 (63. OSSD) are activated. This means, the state of the
OSSD 63 and 64 controls the state of FDX4/5.
Delete "CIP Safety input" in OSSD 3.
Select the block "State of output switching element" from the Device library and place it at the
function input.