Commissioning
Connecting the device to a Modbus master
44
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
RFID channels – process output data
Description
Register
Bit offset
Bit length
Channel 0
Channel 1
Channel 2
Channel 3
Command code
0x0800
0x084C
0x0898
0x08E4
0
16
Loop counter
0x0801
0x084D
0x0899
0x08E5
0
8
Memory area (only UHF)
0x0801
0x084D
0x0899
0x08E5
8
8
Start address
0x0802
0x084E
0x089A
0x08E6
0
32
Length
0x0804
0x0850
0x089C
0x08E8
0
16
Length UID/EPC
0x0805
0x0851
0x089D
0x08E9
0
8
Antenna no.
0x080A
0x0856
0x08A2
0x08EE
0
8
Timeout
0x0806
0x0852
0x089E
0x08EA
0
16
Read fragment no.
0x0807
0x0853
0x089F
0x08EB
0
8
Write fragment no.
0x0807
0x0853
0x089F
0x08EB
8
8
Write data Byte 0
0x080C
0x0858
0x08A4
0x08F0
0
8
Write data Byte 1
0x080C
0x0858
0x08A4
0x08F0
8
8
…
…
…
…
…
…
8
Write data Byte 14
0x0813
0x085F
0x08AB
0x08F7
0
8
Write data Byte 15
0x0813
0x085F
0x08AB
0x08F7
8
8
…
…
…
…
…
…
8
Write data Byte 64
0x082c
0x0878
0x08C4
0x0910
0
8
Write data Byte 65
0x082c
0x0878
0x08C4
0x0910
8
8
…
…
…
…
…
…
8
Write data Byte 126
0x084B
0x0897
0x08E3
0x092F
0
8
Write data Byte 127
0x084B
0x0897
0x08E3
0x092F
8
8