Operation
Using HF bus mode
192
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
9.6
Using HF bus mode
9.6.1
Executing commands in HF bus mode
Set the parameter data.
Select the
HF bus mode
operating mode.
Activate the connected read/write heads.
Set the input data.
Specify the command code.
Set the start address for the command.
Set the required read/write head address.
Send the command to the read/write head.
9.6.2
Replacing bus-capable read/write heads
Remove the faulty read/write head.
Connect the new read/write head with the default address 68 (delivered with …/C53).
If multiple read/write heads are being replaced: Replace the read/write heads in the or-
der in which they were connected.
a
Addresses are allocated in ascending order to the read/write heads in the order in which
the heads were connected. The lowest address is automatically assigned to the next
read/write head with the default address 68 that is connected.
a
If the LED on the read/write head is permanently lit, this indicates that the addressing is
complete.
9.6.3
HF Continuous bus mode – data query and speed
All activated read/write heads are triggered within a bypass time + wait time. The set command
(e.g. Inventory, Read, Write) in Continuous mode is processed within this time. Only one read/
write head sends data to the RFID interface during command execution of all activated read/
write heads. The other read/write heads store the read data for a later query. When the same
read/write head detects a new tag, the data in the buffer of a read/write head is overwritten if it
was not yet sent to the RFID interface.
NOTE
The repeated reading of the same tag is time-triggered. The grouping in the process
output data can be activated in order to prevent the storing of the same UID mul-
tiple times.
The read/write heads do not detect any tags between two queries and when sending data to
the RFID interface. The following table describes the required wait times:
Command
Wait time
Inventory
15 ms
Read
25 ms
Write
35 ms
The default bypass time in HF bus mode is 48 ms.