7.2.4
Modbus TCP slave – setting the IP address
Double-click the Modbus TCP slave.
In the
General
tab enter the IP address of the slave.
Fig. 37: Modbus slave – entering the IP address (here: 192.168.1.61)
7.2.5
Defining Modbus channels (registers)
Defining channel 0 (input data)
Double-click the Modbus TCP Slave.
Select in the tab
Modbus Slave Channel
Ò
Add channel
.
Enter the following values:
n
Name
of channel
n
Access type
: Read holding registers
n
Offset
: 0x0000
n
Length
: 64 registers (128 bytes)
Confirm with
OK
.
Fig. 38: Defining READ registers