(3)
Change the connection of wiring between Comp-IPDU
1
and
Comp-
IPDU
2
, as shown in the below.
1.
When compressor No.1 (front left) is
trouble
:
No change the connection of wiring
2.
When compressor No.2 (front right) is
trouble
:
Change the connection of wiring between
Comp-
IPDU1 and Comp-IPDU2 as shown in the below.
Change the connection of wiring which is connected to the CN21, 23 of Comp-IPDU2
・
Change to CN21 of Comp-IPDU1 from CN21 of Comp-IPDU2
・
Change to CN23 of Comp-IPDU
1
from CN23 of Comp-IPDU2
L1
L2
L3
N
CN530
CN23
CN21
CN23
CN21
- 198 -