Check code
Location
of
detection
Description
System
status
Check code
detection
condition(s)
Main
Check items (locations)
remote
Outdoor 7-segment display
controller
Check
code
Sub-code
Oil level
detection
circuit
trouble
All stop
01: TK1 oil circuit
trouble
02: TK2 oil circuit
trouble
•
•
No temperature
change is detected
by TK1 despite
compressor 1
having
been started.
•
•
•
Check for disconnection of TK1
sensor.
Check resistance characteristics of TK1
sensor.
Check for connection
trouble
involving
TK1 and TK
2
sensors
Check for clogging in oil equalizing
circuit capillary and
trouble
operation in
check valve.
Check for refrigerant entrapment inside
compressor.
•
•
No temperature
change is detected
by TK2 despite
compressor 2
having
been started.
•
•
•
Check for disconnection of TK2 sensor.
Check resistance characteristics of TK2
sensor.
Check for connection
trouble
involving
TK1 and TK
2
sensors
.
Check for clogging in oil equalizing
circuit capillary and
trouble
operation in
check valve.
Check for refrigerant entrapment inside
compressor.
I/F
H16
H16
H07 H07
–
I/F
Low oil level
protection
All stop
Operating compressor
detects continuous
state of low oil level for
about 2 hours.
<All outdoor units in corresponding line
to be checked>
• Check connection and installation of
TK1
and TK
2
sensors.
• Check resistance characteristics of
TK1 and TK
2
sensors.
• Check for gas or oil leak in
same line.
•
C
ompressor casing.
• Check SV3D valve for
trouble
.
• Check oil return circuit of oil separator
for clogging.
• Check oil equalizing circuit for
clogging.
H08
H08
01: TK1 sensor
trouble
02: TK2 sensor
trouble
I/F
Trouble
in
temperature
sensor for oil
level detection
All stop
Sensor resistance is
infinity or zero (open/
short circuit).
• Check connection of TK1 sensor
connector.
• Check resistance characteristics of
TK1 sensor.
• Check for
trouble
in outdoor P.C.
board (I/F).
All stop
Sensor resistance is
infinity or zero (open/
short circuit).
• Check connection of TK2 sensor
connector.
• Check resistance characteristics of
TK2 sensor.
• Check for
trouble
in outdoor P.C.
board (I/F).
H15 H15
–
I/F
TD2 sensor
miswiring
(incomplete
insertion)
All stop
Discharge
temperature of (TD2)
does not increase
despite compressor 2
being in operation.
• Check installation of TD2 sensor.
• Check connection of TD2 sensor
connector and wiring.
• Check resistance characteristics of
TD2 sensor.
• Check for
trouble
in outdoor
P.C. board (I/F).
- 145 -