Ye
s
No
No
Ye
s
No
Ye
s
[F16]
e
s
u
a
C
e
d
o
c
k
c
e
h
C
Check code name
Outdoor pressure sensor
miswiring (P
D
, P
S
)
1.
High-pressure P
D
sensor and low pressure sensor
P
S
are exchanged.
2.
Output voltage of each sensor is zero.
Are connection of
P
D
sensor and P
S
sensor connectors
correct?
Are output
voltage characteristics
of P
D
sensor and P
S
sensor normal?
Are P
D
/P
S
output values
P
D
>P
S
during
compressor
operation?
Correct connection of connectors.
P
D
sensor: CN501, Red
P
S
sensor: CN500, White
Sensor
trouble
Replace
Check compressor
.
Check outdoor I/F P
.C. board.
Failure
Replace
(1) Pressure (Check joint) by pressure gauge
(
2
)
(3
)
Pressure display on 7-segment display
If (1) and (2), (3) are different, a
trouble o
f pressure
sensor itself is considered.
If (2) and (3) are dif
ferent, check interface
P
.C. board.
V
alue can be confirmed by 7-segment
display function on outdoor I/F P
.C. board.
P
D
SW01/02/03=1/1/2
P
S
SW01/02/03=1/2/2
Ye
s
No
Ye
s
No
[F17]
Chec
k code
Chec
k code name
Indoor
TOA sensor
trouble
Cause
T
O
A sensor Open/Shor
t
Is T
O
A
sensor connector
on indoor
P
.C
. board nor
mally
connected?
Are char
acter
istics
of
T
O
A sensor resistance
v
alue nor
mal?
Correct connection of
connector
.
Replace T
O
A
sensor
.
Check indoor P
.C. board.
Failure
→
Replace
*
See "Indoor unit temperature sensor characteristics" on "8-
10
.
Sensor Characteristics".
Ye
s
Ye
s
No
No
[F18]
Chec
k code
Chec
k code name
Indoor
TRA sensor
trouble
Cause
TRA sensor Open/Shor
t
sensor connector
on indoor
P
.C
. board nor
mally
connected?
Is TRA
Are char
acter
istics of
TRA sensor resistance
v
alue nor
mal?
Correct connection of
connector
.
Replace TRA
sensor
.
Check indoor P
.C. board.
Failure
→
Replace
*
See "Indoor unit temperature sensor characteristics" on "8-
.
Sensor Characteristics".
Ye
s
Y
es
Y
es
No
No
Ye
s
No
[F23]
No
Connector: CN500, White
Check code
Check code name
P
S
sensor
trouble
Cause
Output voltage
trouble
of P
S
sensor
Is connection of P
S
sensor connector
correct?
Are output
voltage characteristics
of P
S
sensor
normal?
Is there no leakage
from SV4 valve?
Is not
refrigerant bypassed from
discharge to suction of
4-way valve?
Correct connection of
connector
.
Sensor
trouble
Replace
Check compressor
.
Check 4-way valve.
Replace SV4 valve.
(1) Pressure (Check joint) by pressure gauge
(2)
(3
)
Pressure display on 7-segment display
If (1) and (2), (3) are different, a
trouble o
f pressure
sensor itself is considered.
If (2) and (3) are dif
ferent, check interface
P
.C. board.
Output voltage of I/F P.C. board
Output voltage of I/F P.C. board
- 162 -