Check code
Location
of
detection
Description
System
status
Check code
detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
F08 F08
–
I/F
TO sensor
trouble
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TO
sensor connector.
• Check resistance
characteristics of TO sensor.
• Check for
trouble
in outdoor
P.
C. board (I/F).
F10 –
–
Indoor
unit
Indoor TA
sensor
trouble
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TA
sensor connector and wiring.
• Check resistance
characteristics of TA sensor.
• Check for
trouble
in indoor
P.C. board.
F11 –
–
Indoor
unit
Indoor TF
sensor
trouble
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TF
sensor connector and wiring.
• Check resistance
characteristics of TF sensor.
• Check for
trouble
in indoor
P.C. board.
F12 F12
I/F
TS1/TS3
sensor
trouble
All stop
Sensor resistance is infinity
or zero (open/short circuit).
•
Check connection of TS1/
TS3 sensor connector
• Check resistance
characteristics of TS1
/TS3
sensor.
• Check
for
trouble
F13 F13
01: Compressor 1 side
02: Compressor 2 side
IPDU
TH sensor
trouble
All stop
Sensor resistance is infinity
or zero (open/short circuit).
•
Trouble
in
IPM
built-in
temperature sensor
Replace A3-IPDU P.C.
board.
F15 F15
–
I/F
Outdoor
temperature
sensor wiring
trouble
(T
E
1,
TL
1
)
All stop
During compressor
operation in HEAT mode,
T
L
1 continuously provides
temperature reading higher
than indicated by TL
1
by at
least specified margin for 3
minutes or more.
• Check installation of
T
E
1 and TL
1
sensors.
• Check resistance
characteristics of TE1 and TL
1
sensors.
• Check for outdoor P.C. board
(I/F)
trouble
.
F16 F16
–
I/F
Outdoor
pressure
sensor wiring
trouble
(P
D
, P
S
)
All stop
Readings of high-
pressure P
D
sensor and
low-pressure P
S
sensor
are switched.
Output voltages of both
sensors are zero.
• Check connection of high-
pressure P
D
sensor connector.
•
•
Check connection of low-
pressure P
S
sensor connector.
Check for
trouble
in pressure
sensors P
D
and P
S
.
• Check for
trouble
in outdoor
P.C. board (I/F).
• Check for deficiency in
compressive output of
compressor.
F23 F23
–
I/F
P
S
sensor
trouble
All stop
Output voltage of
P
S
sensor is zero.
• Check for connection
trouble
involving P
S
sensor and P
D
sensor connectors.
• Check connection of P
S
sensor
connector.
• Check for
trouble
in P
S
sensor.
• Check for deficiency in
compressive output of
compressor.
• Check for
trouble
in 4-way
valve.
• Check for
trouble
in outdoor
P.
C. board (I/F).
• Check for
trouble
in SV4 circuit.
F24 F24
–
I/F
P
D
sensor
trouble
All stop
Output voltage of P
D
sensor is zero (sensor
open-circuited).
P
D
> 4.15MPa despite
compressor having been
turned off.
• Check connection of P
D
sensor connector.
• Check for
trouble
in P
D
sensor.
• Check for
trouble
in outdoor
P.
C. board (I/F).
01:
TS1
sersor
trouble
0
3
:
TS3
sersor
trouble
- 143 -