Failure
/Operation Output
Operation
In-operation output: An in-operation indication signal is output as long as at least one indoor unit is in operation
in
the line.
Failure
output: A
Failure
indication signal is output if
check code
occurs in at least one indoor/outdoor unit in
the line.
Note 1: Output Relay (K1, K2) Contact Specifications
•
Output terminals (OUTPUT1, 2) must satisfy the following electrical rating.
•
When connecting a conductive load (e.g. relay coil) to loads K1 and K
2
, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
<Electrical Rating>
220-240 VAC, 10 mA or more, 1A or less
24 VAC, 10 mA or more, 1 A or less (non-conductive load)
OUTPUT1
CN511
PJ20
OUTPUT2
OUTPUT3
TB1
L1
L2
1
2
5
6
4
3
C1
PS
PS
K1
K2
1 2 3 4
ON
OFF
SW16
Optional PCB
Locally procured
(See “NOTE”)
O
utdoor unit
I
nterface PCB
Shield
wire
C1
Attached connection cable 1 (4wires)
CN511
Connector on interface side (green)
K1, K2
Relays
L1
Failure
indication Lamp
L2
Operation indication Lamp
OUTPUT1
Failure
output
OUTPUT2
Operation output
PJ20
Connector on optional PCB side
PS
Power supply unit
TB1
Terminal block