8-
9
. Leakage/Clogging of Refrigerating Cycle Circuit
List of Check Codes Generated upon Occurrence of Leakage/Clogging in Outdoor Cycle
or Oil Circuit Part
Clogging
Leakage
Note:
“XX” represents sub-code
Part
Location of
problem
(see next page)
Unit generating
check code
Detected
problem
and check code
Symptom
Outdoor PMV1
A
Corresponding unit
Activation of high-pressure protection
Activation of low-pressure protection
Discharge temp.
trouble
(TD1)
Discharge temp.
trouble
(TD2)
P20
H06
P03
P17
Rise of pressure
Fall of pressure
Rise of discharge temp.
(compressor 1)
Rise of discharge temp.
(compressor 2)
Check valve in discharge pipe
convergent section
B
Corresponding unit
High-pressure protection
trouble
High-pressure SW system
trouble
P20
P04-XX
Abnormal rise of pressure
Check valve in discharge pipe
C
Corresponding unit
High-pressure SW system
trouble
P04-XX Abnormal rise of pressure
O
il-equalization circuit
Capillary
Strainer
D
Corresponding unit
Oil level detection circuit
trouble
Oil level low detection and protection
H16-XX
H07
Oil circuit
trouble
or oil level
low
SV3D valve
SV3D valve circuit capillary
Strainer
E
Corresponding unit
Oil level low detection and protection H07
Oil level low
Part
Unit generating
check code
Detected
problem
and check code
Symptom
Outdoor PMV1
A
Corresponding unit
Outdoor liquid backflow
trouble
Oil level low detection and protection
P13
H07
Refrigerant entrapment
Check valve in discharge pipe
B
n
o
it
c
e
s
t
n
e
g
r
e
v
n
o
c
Corresponding unit
Oil level low detection and protection
Compressor breakdown
Compressor
trouble
(lockup)
H07
H01-XX
H02-XX
Refrigerant entrapment
Check valve in discharge pipe
C
Corresponding unit
Oil level low detection and protection
Compressor breakdown
Compressor
trouble
(lockup)
H07
H01-XX
H02-XX
Refrigerant entrapment
Location of
problem
(see next page)
- 190 -