Ye
s
Ye
s
No
No
No
No
Ye
s
Ye
s
No
No
Ye
s
[P17]
Cause
Check code
Check code name
Discharge temp
TD2
trouble
1.
Outdoor unit service valve closed
2.
Outdoor PMV
trouble
3.
TD
sensor
trouble
4.
Refrigerant shortage, clogging of refrigerant circuit
5.
4-way valve
trouble
6.
SV4 circuit leakage, misinstallation
Are service valves
of gas and liquid
sides fully opened?
Open service valves fully
.
Repair outdoor PMV
.
Replace TD2
sensor
.
Check 4-way valve.
Correct installation of
valve coil.
Replace SV42 valve.
Correct wiring
Refrigerant shortage,
clogging, pipe breakage
Are indoor units of a
dif
ferent refrigerant line
connected?
Are
characteristics
of TD2
sensor
resistance
normal?
Does discharge
refrigerant gas bypass
to suction side through
4-way valve?
Connectors: PMV1: CN300,
PMV4: CN303
Ye
s
(Check it using the miswiring check
function of the outdoor unit.)
(Check there is no pipe breakage, and
then recharge the refrigerant.)
Is outdoor PMV normal?
1. Connector connection
2. Wiring
Coil
3.
4. V
alve body
5. Outdoor I/F P
.C. board
SV4 circuit
1.
Are SV41, SV42
valve coils installed correctly?
Is SV42 circuit sealed
2.
correctly (no leakage)?
Ye
s
Ye
s
No
No
No
Ye
s
No
No
Ye
s
[P15]
Cause
Check code
Check code name
Gas leak detection
TD condition (Sub-code: 02)
1.
Outdoor unit service valve closed
2.
Outdoor PMV
trouble
3.
TD
sensor
trouble
4.
SV4 circuit
trouble
5.
Refrigerant shortage, clogging refrigerant circuit
Are service
valves of gas
and liquid sides
fully opened?
Open service valves fully
.
Repair outdoor PMV
.
Replace
TD1
and
TD2
sensor.
Correct wiring.
Refrigerant shortage,
clogging, pipe breakage.
Repair SV4 valve circuits.
(Coil, valve body
, coil installation,
disconnection of cable, etc.)
Ye
s
(Check it using the miswiring check
function of the outdoor unit.)
(Check there is no clogging and pipe
breakage, and then recharge refrigerant.)
Connectors: PMV1: CN300,
PMV4: CN303
Are
characteristics
of
TD1
and
TD2
sensor resistance
normal?
Is SV4 valve
circuit normal?
(Coil misinstallation,
valve leakage)
Are not indoor
units in dif
ferent
refrigerant circuit
connected?
Is outdoor PMV normal?
Connector connection
1.
Wiring
2.
Coil
3.
4. V
alve body
5. Outdoor I/F P
.C. board
*
S
ee “O
utd
oo
r unit tempe
ratu
re
sen
sor
characteristics”
on
“8-
10
. Sensor
Characteristics”.
* Se
e “
O
u
tdo
or
un
it
te
mp
er
at
ur
e
senso
r
characteristics” on
“8-
10
.
Sensor Characteristics”.
- 177 -