[H16]
Chec
k code
Cause
Chec
k code name
Oil level detection circuit
trouble
TK2 temperature detective circuit
trouble
(Sub-code:
02)
1.
Coming-off of
TK2 sensor, miswiring,
characteristics
trouble
of resistance value
2.
Oil-equalization circuit
trouble
(
Capillary
clogging, strainer clogging
)
3.
Refrigerant stagnation in the compressor shell
No
Y
es
Y
es
Y
es
No
No
No
trouble
Trouble
Is not
TK2 sensor
detached?
Is there
no miswiring or
misinstallation on
TD1/TD2/TK1/TK2/
sensors?
Are
characteristics
of
TK2
sensor
resistance
value
normal?
Correct installation of
sensor.
Sensor
trouble
Replace clogging part.
Check I/F
P
.C.
board
Correct miswiring/misinstallation.
TD1:
CN502, white
TD2:
CN503, pink
TK1:
CN531, black
TK2: CN532, green
Start a test operation in COOL or HEAT mode.
Display
TK2 sensor temperature on 7-segment display with
SW01/02/03=[1] [13] [2].
Check
TK2 sensor temp approx.
10 minutes after compressor 2 has operated.
If low temperature continues (approximately outside temp) or temperature has
little change, a clogging of strainer of oil-equalization circuit, clogging of
capillary tube, or malfunction of check valve is considered.
After resetting
the power
*See
"Outdoor
unit
temperature
sensor
characteristics"
on
"8-
.
Sensor
Characteristics".
↓
↓
(TK2)
Capillary
tube
Strainer
Comp.
2
(inverter)