6-1-1.
Control Specifications
NO.
Item
Specification
s
outline
Remarks
1
Upon power
supply reset
1.
Identification of outdoor unit
When the power supply is reset, the outdoor unit is identified, and control is
redirected according to the identification result.
2.
Indoor fan speed and air flow direction control availability settings
Settings such as indoor fan speed and air flow direction control availability are
replaced on the basis of EEPROM data.
3.
If power supply reset is performed in the wake of a
trouble
, the check code is
cleared. If the abnormality persists after the Start/Stop button on the remote
controller is
pressed to resume operation, the check code is redisplayed on the
remote
controller.
2
Operation
selection
1. The operation mode changes in response to an operation selection command
issued via the remote controller.
3
Room temp.
control
1. Adjustment range - remote controller temperature setting (°C)
2. In heating operation, the temperature setting may be fine-tuned via the DN code
“06”.
Factory default
Shift in heating suction
temperature
(not applicable to
remote controller
thermo
stat
operation)
4
Automatic
capacity control
1. The outdoor unit determines the operational capacities of indoor units according
to the difference between T
A
and T
S
.
T
S
: Temperature
setting
T
A
: Room temperature
Remote controller command
Control outline
STOP
Air conditioner shutdown
FAN
Fan operation
COOL
Cooling operation
DRY
Drying operation
HEAT
Heating operation
COOL/DRY
HEAT
Wired type
18~29
18~29
Wireless type
18~30
16~30
SET DATA
0
2
4
6
Temperature setting adjustment
+0°C
+2°C
+4°C
+6°C
SET DATA
2
SD
SB
S9
S7
S5
S3
S0
Cooling
+2
+1
T
S
-1
S3
S5
S7
S9
SB
SD
SF
S0
Heating
+1
T
S
-2
-1
T
A
(°C)
T
A
(°C)
6.
Applied control
and Functions
6-
1
. Applied Control
for
Indoor
Unit
- 48 -