Using indoor unit indicators (receiving unit light block) (wireless type)
To identify the check code, check the 7-segment display on the
outdoor
unit. To check for check codes not
displayed on the 7-segment display, consult the “List of Check Codes (Indoor Unit)” in “8-2. Troubleshooting
Method”.
: Goes off
: Lighting
: Blinking (0.5 seconds)
Cause of
check code
e
d
o
c
k
c
e
h
C
k
c
o
l
b
t
h
g
i
L
–
Power turned off or
trouble
in wiring between receiving and indoor units
E01
Receiving unit
Trouble
or poor contact in
wiring between receiving and
indoor units
E02
Troubled
reception
Troubled
transmission
E03
Loss of communication
E08
Duplicated indoor unit No. (address)
Setting
trouble
E09
Duplicated master remote controller
E10
Indoor unit inter-MCU communication
trouble
E12
Automatic address starting
trouble
E18
Trouble
or poor contact in wiring between indoor units, indoor power turned off
E04
Trouble
or poor contact in wiring between indoor and outdoor units
(loss of indoor-outdoor communication)
E06
Troubled
reception in indoor-outdoor communication (
Signal lack
of indoor unit)
E07
Troubled
transmission in indoor-outdoor communication
E15
Indoor unit not found during automatic address setting
E16
Too many indoor units connected/overloading
E19
Trouble
in number of outdoor unit
E20
Detection of refrigerant piping communication
trouble
during automatic address setting
E31
IPDU communication
trouble
, sub MCU communication
trouble
P01
Indoor AC fan
trouble
P10
Indoor overflow
trouble
P12
Indoor DC fan
trouble
P13
Outdoor liquid backflow detection
trouble
P03
Outdoor discharge (TD1) temperature
trouble
P04
Activation of outdoor high-pressure SW
P05
Open phase/power failure
Inverter DC voltage (Vdc)
trouble
MG-CTT
trouble
P07
Outdoor heat sink overheating
trouble
- Poor cooling of electrical component (
IPM
) of outdoor unit
P15
Gas leak detection - insufficient refrigerant charging
P17
Outdoor discharge (TD2) temperature
trouble
P19
Outdoor 4-way valve reversing
trouble
P20
Activation of high-pressure protection
P22
Outdoor fan IPDU
trouble
P26
Outdoor
IPM
short-circuit
trouble
P29
Compressor position detection circuit
trouble
P31
Shutdown of other indoor unit in group due to
trouble
(group follower unit
trouble
)
Operation Timer
Ready
All lights out
Blinking
Operation Timer
Ready
Blinking
Operation Timer
Ready
Alternate blinking
Operation Timer
Ready
Alternate blinking
Operation Timer
Ready
MG-CTT: Magnet contactor