Check code
Location
of
detection
Description
System status
Check code
detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
P1
9
P1
9
Detected outdoor unit No.
I/F
4-way valve
reversing
trouble
All stop
Abnormal refrigerating cycle
data is collected during
heating operation.
• Check for
trouble
in main
body of 4-way valve.
•
•
Check for coil
trouble
in
4-way valve and loose
connection of its
connector.
Check resistance
characteristics of TS1
and TE1 sensors.
• Check output voltage
characteristics of P
D
and
P
S
pressure sensors.
• Check for wiring
trouble
involving TE1 and TL
1
sensors.
P
20
P
20
–
I/F
Activation of
high-pressure
protection
All stop
<During cooling operation>
P
D
sensor detects pressure
equal to or greater than
3.85
MPa.
<During heating operation>
P
D
sensor detects pressure
equal to or greater than 3.6
MPa.
• Check for defect in P
D
pressure sensor.
• Check service valves (gas
side, liquid side) to confirm
full opening.
• Check for
trouble
in outdoor
fan.
• Check for
trouble
in outdoor
fan motor.
• Check outdoor PMV
(PMV1
,
4)
for clogging.
• Check indoor/outdoor heat
exchangers for clogging.
• Check for short-circuiting
of outdoor suction/
discharge air flows.
• Check SV2 circuit for
clogging.
• Check for
trouble
in outdoor
P.
C. board (I/F).
• Check for
trouble
in indoor
fan system (possible cause
of air flow reduction).
• Check opening status of
indoor PMV.
• Check indoor-outdoor
communication line for
wiring
trouble
.
• Check for
trouble
operation
of check valve in discharge
pipe convergent section.
• Check gas balancing SV4
valve circuit.
• Check SV5 valve circuit.
• Check for refrigerant
overcharging.
- 150 -