[H07]
e
s
u
a
C
e
d
o
c
k
c
e
h
C
Check code name
Oil level down detection
protection
1.
Miswiring or misinstallation of
TK1, TK2
sensors
2.
TK1, TK2
sensor
trouble
3.
Gas leak or oil leak in a line
4.
SV3D
valve
trouble
5.
Clogging of oil return circuit from oil separator
6.
Clogging of oil-equation circuit system
No
No
No
Ye
s
Ye
s
Ye
s
Ye
s
No
No
Ye
s
No
Ye
s
(Check with miswiring check function of outdoor unit.)
Ye
s
No
No
Ye
s
No
Ye
s
No
Ye
s
Ye
s
No
No
Cleaning
Cleaning
[H06]
Cause
Check code
Check code name
Low-pressure protective operation
1.
Service valve close
2.
P
S
sensor
trouble
3.
SV2, SV4 circuit
trouble
4.
Miswiring of communication between indoor and
outdoor
5.
Indoor/outdoor fan and condenser
trouble
6.
Indoor/outdoor PMV clogging
7.
Indoor/outdoor heat exchanger clogging
8.
Refrigerant shortage
Are
service valves of
gas and liquid pipe of
outdoor unit fully
opened?
Are
characteristics of
low-pressure sensor
normal?
Are SV2 and SV4
circuits normal?
Is any indoor unit
in a dif
ferent line
connected?
Does indoor
fan normally operate
in cooling season?
Is there
clogging of indoor air filter
or heat exchanger?
Is indoor PMV
normal?
Is outdoor fan
normally operated in
heating season?
Is there
clogging of outdoor heat
exchanger?
Is outdoor PMV
normal?
Is connector
connection or coil
normal?
Is there clogging
on whole valve?
Are
following items
concerned to indoor fan
motor normal?
1. Connector connection
2. Condenser
3. Motor
4. Fan
Open service valves
fully
.
Exchange low-pressure
sensor
.
Correct SV2 and SV4
circuits.
Correct wiring.
Repair
failure
parts.
Check indoor P
.C. board.
Failure
Replace
Ye
s
Refrigerant shortage or clogging or pipe deformed
Repair
failure
parts.
Repair
failure
parts.
Refrigerant shortage,
clogging, pipe deformed
Replace PMV body
.
Check outdoor I/F P
.C. board.
Failure
Replace
In cooling season, go to (A)
In heating season, go to (B)
(A) Cooling
(B) Heating
No
Check miswiring, misinstallation and connector connection.
No
*
1. Pressure by pressure gauge (Check joint)
Pressure display on 7-segment display
2.
3. Output voltage of I/F P.C. board
If 1 and 2, 3 are different, a
failure
of pressure sensor is considered.
If 2 and 3 are different, check I/F P.C. board.
Is indoor fan system normal?
Fan crack•
• Fan coming-of
f
Correct
miswiring
and
misinstallation.
TK1:
CN531,
black
TK2: CN532,
green
Are
TK1
and
TK2 sensors
of
the
trouble-detected
unit
correctly
connected?
Are
all
the
sensors
properly
connected?
No
Yes
Are
characteristics
of
TK1
and
TK2
of
trouble-detected
unit
normal?
Sensor
trouble
replace
No
Yes
*See
"Outdoor
unit
temperature
sensor characteristics"
on
"8-10.
Sensor
Characteristics."
Refrigerant
shortage
or oil shortage
(Refigerant
recharging,
refill oil)
(*1)(*2)
Check
clogging of
oil
return
circuit
from
oil separator.
(Capillary tube,strainer)
Check
clogging
of
SV3D
valve.
Replace
trouble
part.
Clogging
No
clogging
(*3) Check
clogging
of
oil
equalization
circuit.
Replace
trouble
part.
Clogging
No
clogging
- 166 -