Compressor position detective
circuit
trouble
1.
Wire/connector connection
trouble
2.
Compressor
trouble
3.
A3-IPDU P
.C. board
trouble
Other indoor
trouble
(Group follower unit
trouble
)
Another indoor unit in the group is abnormal.
Sub-code:
01: Compressor 1, 02: Compressor 2
Are connector
connection and wiring
normal?
Is the unit
earth
ed?
Is not winding
shorted? (Is winding
resistance 0.1 to
1.0
Ω
?)
Is not winding
opened?
Check and correct circuit and
cables such as wiring to
compressor
, etc.
Compressor
trouble
Replace
Compressor
trouble
Replace
Compressor
trouble
Replace
Check
A3-IPDU P
.C. board.
Failure
Replace
When the header unit of the group detected
check code
[E03], [L03], [L07] or [L08], the follower unit of the group
displays [P31]
check code
and stops.
There are no check code display and alarm record of the main remote controller.
Ye
s
No
Ye
s
No
Ye
s
No
Ye
s
No
[P26]
Cause
Check code
Check code name
IPM
short-circuit protection
trouble
1.
Outdoor unit power
trouble
2.
A3-IPDU
trouble
/Wire connection
trouble
3.
Compressor
trouble
4.
A3-IPDU
P.C. board
trouble
Is power voltage
of outdoor unit
normal?
Is wire connector
connection on
INV P
.C. board
normal?
Is there no fusing
of
AC
31.5A
fuse?
Is compressor
normal?
Correct power line.
Correct connection of wire
connector
.
Replace
A3-IPDU P.C.
board.
Replace compressor
.
Replace A3-IPDU
P
.C.
board.
Sub-code:
01: Compressor 1, 02: Compressor 2
- 180 -