Check code
detected by IPDU featuring in SMMS-
e
S
tand
alone type
outdoor unit - typical examples)
Note: The above check codes are examples only, and different check codes may be displayed depending on the outdoor unit configuration
Check code
Display of receiving unit
Typical
problem
site
Description of
check code
Outdoor 7-segment display
TCC-LINK
central control
or main remote
controller
display
Indicator light block
Sub-code
Flash
F13
01: Compressor 1
02: Compressor 2
T
L
A
3
1
F
trouble
in temperature
sensor built into indoor
IPM
(TH)
Temperature sensor built into indoor
IPM
(TH)
has been open/short-circuited.
H01
01: Compressor 1
02: Compressor 2
n
w
o
d
k
a
e
r
b
r
o
s
s
e
r
p
m
o
C
1
0
H
Inverter current (Idc) detection circuit detects
overcurrent.
H02
01: Compressor 1
02: Compressor 2
H02
Compressor
trouble
(lockup)
Compressor lockup is detected
H03
01: Compressor 1
02: Compressor 2
H03
Current detection circuit
trouble
Abnormal current is detected while inverter
compressor is turned off.
P04
01: Compressor 1
02: Compressor 2
T
L
A
4
0
P
Activation of high-pressure
SW
High-pressure SW is activated.
P07
01: Compressor 1
02: Compressor 2
T
L
A
7
0
P
Heat sink overheating
trouble
Temperature sensor built into
IPM
(TH) detects
overheating
or has been short-circuited.
P22
1
0:Element short
circuit
1
1:Position detection circuit
trouble
1
3:Motor lock
trouble
1
4:Motor current
trouble
1
C:
TH
Sensor temperature
trouble
1
D:TH Sensor short circuit/release
trouble
1
E:Vdc voltage
trouble
Outdoor fan IPDU detects
trouble
.
Outdoor fan IPDU
trouble
T
L
A
2
2
P
P26
01: Compressor 1
02: Compressor 2
T
L
A
6
2
P
Activation of
IPM
short-circuit protection
Short-circuit protection for compressor motor
driver circuit components is activated (momentary
overcurrent).
P29
01: Compressor 1
02: Compressor 2
T
L
A
9
2
P
Compressor position
detection circuit
trouble
Compressor motor position detection
trouble
is detected.
Operation Timer Ready
- 132 -