Remove the electrical junction box cover (situated at the bottom right hand side of the unit) by removing 
the single junction box cover screw. Bring supply wiring into the unit through the knockout in the bottom 
of the junction box securing the entry point with a connector.

 Power supply wire should be 14AWG 

and protected by a 15AMP over current protector.

 Connect line input to black lead, neutral to white 

lead and ground to pillar marked G inside junction box.  

 

Start-up 

Set the fan speed switch to either 

I (low speed) 

or 

II (high speed) 

and activate the system thermostat 

(field supplied), because of the integral low limit aquastat, it may take several minutes before the fan is 
activated. When the fan does come on, ensure that the switch is operational by moving position to 

(off),

 then to 

II (high speed). 

Best results are obtained by leaving the switch in the  

position and 

reserving 

II 

for a quick heat up or in extreme conditions. If the unit is not operating please refer to the 

trouble shooting tips at the end of this manual. 

Unit operation. 

This Pocket Wall Unit has 2 different controls. 
1. An internal aquastat, not operated by the user. 
2. A surface mounted rocker switch (situated behind the access door) for the user to operate the fan 
speeds. Min / Off / Max. 
Press “

I

” for Min. fan speed, press “

0

” for off, press “

II

” for Max. Fan speed. 

Room thermostat control 

This Pocket Wall Unit may be run by a field supplied remote wall mounted room thermostat wired into the 
power supply. Refer to the instructions provided with the thermostat selected.. One thermostat can be 
used to control up to four heater appliances. This field supplied thermostat should be a line voltage 
thermosat. 
Alternatively, field supply a low voltage room thermostat that would be wired directly to the circulator for 
the zone that the PWU units are installed on. On a call for heat, the circulator would come on and the unit 
mounted aquatstat would bring the fan on once the coil temperature exceeded the lower threshold. 

 

Unit maintenance 

The Smiths Environmental Products PWU recess units are designed for years of trouble free operation. 

 

If servicing is required, please contact the installing contractor or 
 

Smiths Environmental Products 

Customer Service 

300 Pond Street 

Randolph, Ma 02368 

Phone: 269 925 8818 

 

Troubleshooting tips 

If the unit fails to operate: 
1. Verify that the supply voltage is 120V AC, all wires are connected and the fan switch is in the 

or 

II 

position. 
2. Verify that hot water is going to and through the unit at 110°F or above. Both supply and return tubes 
should be hot. If the return is not hot, the coil is air locked, which will prevent the fan from operating when 
unit is set to heating mode. Bleed air from the coil if necessary. The unit should run. 
3.  If the PWU still does not run, replace the aquastat. 

 

 Caution: 

 ELECTRICAL SHOCK MAY RESULT. ISOLATE FROM POWER BEFORE OPENING OR 
SERVICING THIS UNIT 

 

 

Nov 09    

 

 

 

                                                                   PWU 

 

   

 

 

 

 

 

 

 

 

 

 

 
 

 

 
 
 
 
 
 
 

PWU 4/6 
PWU 6/8 

PWU 8/10 

PWU 13/15 

Installation & user Guide

 