 The condensing unit must only be used for 

its designed purpose(s) and within its scope of 

application. 

  Under  all  circumstances,  the  EN378  (or  

other  applicable  local  safety  regulation) 

requirements must be fulfilled.
The condensing unit is delivered under nitro-

gen gas pressure (1 bar) and hence it cannot 

be connected as it is; refer to the «installation»

 

section for further details. 
The condensing unit must be handled with cau-

tion  in  the  vertical  position  (maximum  offset 

from the vertical : 15°)

FRCC.EI.026.A2.02 © Danfoss Commercial Compressors 11/12

1

MADE IN INDIA

OP-SMLZ015ME

Code no.:

Application

Refrigerant

M.W.P. HP

114X70..

MBP

(1) R404A, R507A

(1) 28 bar

             LP (1)  7  bar

IP54

(2) R134a

(2) 23 bar

(2)  5  bar

Voltage

380V - 400 ~ 3 50Hz

LRA

51

20

MCC

Serial No.

Barcode Serial No: 

123456BS0310 

118UXXXX

A

B

C

D

E
F

G

K

H

I

J

INSTRUCTIONS 

OPTYMA™ SlIM PACk OP-SMlZ

Installation  and  servicing  of  the 
condensing  units  by  qualified 

personnel  only.  Follow  these  instructions 
and sound refrigeration engineering practice 
relating  to  installation,  commissioning, 
maintenance and service.

A

:   Model

B

:   Code number 

C

:   Application, Protection

D

:   Refrigerant 

E

:   Housing Service Pressure

F

:   Supply  voltage,  Locked  Rotor  Ampere, 

Maximum Current Consumption

G

:   Serial Number and bar code

H

:   Cable entry ports

I

:   Suction port

J

:   Liquid port

k

:   Microchannel heat exchanger

L

M

N

O

[mm]

[mm]

[mm]

[mm]

250

650

550

550

Picture 1 : Minimum mounting distances

Picture 2 

Picture 3 

Mounting bolts (not supplied)

1 – Introduction

These  instructions  pertain  to  Optyma  conden-

sing units OP-SMLZ (R507A, R404A, R134a, R22)

used for refrigeration systems. They provide ne-

cessary information regarding safety and proper 

usage of this product

The condensing unit includes following:

  •  Scroll compressor

  •  Microchannel heat exchanger

  •  Dual pressure switches

  •  Service valves Suction/ liquid

  •  Fan and compressor capacitors

  •  Weather proof housing

  •  Filter drier

  •  Cranckcase heater for compressor

  •  Receiver with stop valve

  •  Sight glass

2 – Handling and storage

  •  It  is  recommended  not  to  open  the  packaging 

before the unit is at the final place for installation.

  •  Handle the unit with care. The packaging al-

lows for the use of a forklift or pallet jack. Use 

appropriate and safe lifting equipment. 

  •  Store and transport the unit in an upright position.

  •  Store the unit between -35°C and 50°C.

  •  Don’t expose the packaging to rain or corro-

sive atmosphere.

  •  After  unpacking,  check  that  the  unit  is  com-

plete and undamaged.

3 – Installation precautions

 Do not braze as long the condensing unit is 

under pressure.

 Never place the unit in a flammable atmosphere 

 Place the unit in such a way that it is not blocking 

or hindering walking areas, doors, windows or similar.

  •  Ensure adequate space around the unit for air 

circulation  and  to  open  doors.  Refer  to  pic-

ture1 for minimal values of distance to walls.

  •  Avoid installing the unit in locations which are dai-

ly exposed to direct sunshine for longer periods.

  •  Avoid  installing  the  unit  in  aggressive  and 

dusty environments.

  •  Ensure  a  foundation  with  horizontal  surface 

(less than 3° slope), strong and stable enough 

to  carry  the  entire  unit  weight  and  to  elimi-

nate vibrations and interference.

  •  The  unit  ambient  temperature  may  not  ex-

ceed 50°C during off-cycle.

  •  Ensure that the power supply corresponds to 

the unit characteristics (see nameplate).

  •  When  installing  units  for  HFC  refrigerants, 

use  equipment  specifically  reserved  for  HFC 

refrigerants which was never used for CFC or 

HCFC refrigerants.

  •  Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

  •  Use clean and dehydrated system components.

  •  The  suction  piping  connected  to  the  com-

pressor  must  be  flexible  in  3  dimensions  to 

dampen  vibrations.  Furthermore  piping  has 

to be done in such a way that oil return for the 

compressor  is  ensured  and  the  risk  of  liquid 

slug over in compressor is eliminated.

4 – Installation

  •  The installation in which the condensing unit 

is installed must comply to EEC Pressure direc-

tive (PED) no. 97/23/EC. The condensing unit 

itself is not a ”unit” in the scope this directive.

  •  The unit must be securely installed on a stable 

and rigid support, and fixed from the begin-

ning. See picture 2.

  • 

 It is recommended to install the unit on rub-

ber  grommets  or  vibration  dampers  (not 

supplied).

  •  Slowly  release  the  nitrogen  holding  charge 

through the schrader port.

  •  Connect the unit to the system as soon as pos-

sible to avoid oil contamination from ambient 

moisture.

  •  Avoid material entering into the system while 

cutting  tubes.  Never  drill  holes  where  burrs 

cannot be removed.

  •  Braze with great care using state-of-the-art tech-

nique and vent piping with nitrogen gas flow.

  •  Connect  the  required  safety  and  control  de-

vices. When the schrader port is used for this, 

remove the internal valve.

  •  It  is  recommended  to  insulate  the  suction 

pipe up to the compressor inlet with 19 mm 

thick insulation.