background image

2

FRCC.EI.026.A2.02 © Danfoss Commercial Compressors 11/12

Instructions

5 – Leak detection

  Never  pressurize  the  circuit  with  oxygen  or 

dry air. This could cause fire or explosion.

  •  Do not use dye for leak detection.

  •  Perform a leak detection test on the complete 

system.

  •  The maximum test pressure is 32 bar.

  •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

  •  Never use the compressor to evacuate the system.

  •  Connect a vacuum pump to both the LP & HP 

sides.

  •  Pull down the system under a vacuum of 500 

μm Hg (0.67 mbar) absolute.

  •  Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

7 – Electrical connections

  •  Switch off and isolate the main power supply.

  •  Ensure that power supply can not be switched 

on during installation.

  •  All electrical components must be selected as 

per local standards and unit requirements.

  •  Refer to wiring diagram for electrical connec-

tions details.

  •  Ensure that the power supply corresponds to 

the  unit  characteristics  and  that  the  power 

supply  is  stable  (nominal  voltage  ±10%  and 

nominal frequency ±2,5 Hz).

  •  Dimension  the  power  supply  cables  accor-

ding to unit data for voltage and current.

  •  Protect the power supply and ensure correct 

earthing.

  •  Make  the  power  supply  according  to  local 

standards and legal requirements.

  •  The unit is equipped with high and low pres-

sure  switches,  which  directly  cut  the  power 

supply to the compressor in case of activation.

Parameters for high and low pressure cut outs 

should  be  set  by  installer  considering  com-

pressor model, refrigerant and application.

For units with a 3-phase scroll compressor, cor-

rect  phase  sequence  for  compressor  rotation 

direction shall be observed.

  •  Determine  the  phase  sequence  by  using  a 

phase  meter  in  order  to  establish  the  phase 

orders of line phases L1, L2 and L3.

  •  Connect  line  phases  L1,  L2  and  L3  to  main 

switch terminals T1, T2 and T3 respectively.

8 – Filling the system

  •  Wear protective stuff like goggles and protec-

tive gloves.

  •  Never  start  the  compressor  under  vacuum. 

Keep the compressor switched off.

  •  Before charging the refrigerant, verify that the 

oil level is between ¼ and ¾ on the compressor 

oil sight glass. If additional oil is required please 

refer to the compressors label for type of oil.

  •  Use only the refrigerant for which the unit is 

designed for.

  •  Fill  the  refrigerant  in  liquid  phase  into  the 

condenser  or  liquid  receiver.  Ensure  a  slow 

charging of the system to 4 – 5 bar for R404A / 

R507A or R22 and approx. 2 bar for R134a.

  •  Do not put liquid refrigerant through suction line.

  •  It is not allowed to mix additives with the oil 

and/or refrigerant

  •  The remaining charge is done until the instal-

lation  has  reached  a  level  of  stable  nominal 

condition during operation.

  •  Never leave the filling cylinder connected to 

the circuit.

9 – Verification before commissioning

  Use  safety  devices  such  as  safety  pressure 

switch  and  mechanical  relief  valve  in  com-

pliance  with  both  generally  and  locally  appli-

cable  regulations  and  safety  standards.  Ensure 

that they are operational and properly set.

  Check  that  the  settings  of  high-pressure 

switches and relief valves don’t exceed the maxi-

mum service pressure of any system component.

  •  Verify that all electrical connections are properly 

fastened and in compliance with local regulations.

  •  When a crankcase heater is required, it must 

be  energized  at  least  12  hours  before  initial 

start-up  and  start-up  after  prolonged  shut-

down or belt type crankcase heaters.

10 – Start-up

  •  Never  start  the  unit  when  no  refrigerant  is 

charged.

  •  All service valves must be in the open position.

See picture 3.

  •  Check  compliance  between  unit  and  power 

supply.

  •  Check that the crankcase heater is working.

  •  Check that the fan can rotate freely.

  •  Check that the protection sheet has been re-

moved from the backside of condenser.

  •  Balance the HP/LP pressure.

  •  Energize  the  unit.  It  must  start  promptly.  If 

the  compressor  does  not  start,  check  wiring 

conformity,  voltage  on  terminals  and  se-

quence phase.

  •  Eventual reverse rotation of  a 3-phase com-

pressor  can  be  detected  by  following  phe-

nomena;  unit  doesn’t  start,  the  compressor 

doesn’t  build  up  pressure,  it  has  abnormally 

high sound level and abnormally low power 

consumption.  In  such  case,  shut  down  the 

unit immediately and connect the phases to 

their proper terminals.

  •  If the rotation direction is correct the low pres-

sure  indication  on  the  low  pressure  gauge 

shall show a declining pressure and the high 

pressure  indication  on  the  high  pressure 

gauge shall show an increasing pressure.

11 – Check with running unit

  •  Check the fan rotation direction. Air must flow 

from the condenser towards the fan.

  •  Check current draw and voltage.

  •  Check  suction  superheat  to  reduce  risk  of 

slugging.

  •  When a sight glass is provided observe the oil 

level at start and during operation to confirm 

that the oil level remains visible.

  •  Respect the operating limits.

  •  Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 

measures such as tube brackets.

  •  When  needed,  additional  refrigerant  in  liquid 

phase may be added in the low-pressure side as 

far away as possible from the compressor. The 

compressor must be operating during this pro-

cess.

  •  Do not overcharge the system.

  •  Never release refrigerant to atmosphere.

  •  Before  leaving  the  installation  site,  carry  out 

a  general  installation  inspection  regarding 

cleanliness, noise and leak detection.

  •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference 

for future inspections.

12 – Maintenance

 Always switch off the unit at main switch be-

fore remove fan panel.

  Internal  pressure  and  surface  temperature 

are dangerous and may cause permanent injury.

Maintenance  operators  and  installers  require 

appropriate skills and tools. Tubing temperature 

may exceed 100°C and can cause severe burns.

  Ensure  that  periodic  service  inspections  to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related problems, following

Periodic  maintenance is recommended:

  •  Verify that safety devices are operational and 

properly set.

  •  Ensure that the system is leak tight.

  •  Check the compressor current draw.

  •  Confirm that the system is operating in a way 

consistent  with  previous  maintenance  re-

cords and ambient conditions.

  •  Check  that  all  electrical  connections  are  still 

adequately fastened.

  •  Keep the unit clean and verify the absence of 

rust  and  oxidation  on  the  unit  components, 

tubes and electrical connections.

The  condenser  must  be  checked  at  least  once 

a  year  for  clogging  and  be  cleaned  if  deemed 

necessary.  Access  to  the  internal  side  of  the 

condenser  takes  place  through  the  fan  panel. 

Microchannel  coils  tend  to  accumulate  dirt  on 

the  surface  rather  than  inside,  which  makes 

them easier to clean than fin-&-tube coils.

  •  Switch off the unit at main switch before re-

move any panel from the condensing unit.

  •  Remove  surface  dirt,  leaves,  fibres,  etc.  with 

a vacuum cleaner, equipped with a brush or 

other  soft  attachment.  Alternatively,  blow 

compressed air through the coil from the in-

side out, and brush with a soft bristle. Do not 

use a wire brush. Do not impact or scrape the 

coil with the vacuum tube or air nozzle.

If the refrigerant system has been opened, the 

system has to be flushed with dry air or nitrogen 

to remove moisture and a new filter drier has to

be installed. If evacuation of refrigerant has to 

be done, it shall be done in such a way that no 

refrigerant can escape to the environment.

13 - Warranty

Always transmit the model number and serial num-

ber with any claim filed regarding this product.

The product warranty may be void in following 

cases:

  •  Absence of nameplate.

  •  External  modifications;  in  particular,  drilling, 

welding, broken feet and shock marks.

  •  Compressor opened or returned unsealed.

  •  Rust,  water  or  leak  detection  dye  inside  the 

compressor.

  •  Use of a refrigerant or lubricant not approved 

by Danfoss.

  •  Any  deviation  from  recommended  instruc-

tions pertaining to installation, application or 

maintenance.

  •  Use in mobile applications.

  •  Use in explosive atmospheric environment.

  •  No model number or serial number transmit-

ted with the warranty claim.

14 – Disposal

Danfoss recommends that condensing 

units  and  oil  should  be  recycled  by  a 

suitable company at its site.

Reviews: