Indoor other error
Indoor P
.C. board error
This error is detected during operation of air conditioner of IC10 non-volatile memory (EEPROM) on
indoor unit P
.C.board. Replace service P
.C. board.
* If EEPROM was not inserted when power was turned on or it is absolutely impossible to read/write
EEPROM data, the automatic address mode is repeated.
[SET
DA
T
A]
is displayed
on remote
controller
.
[SET
DA
T
A]
disappears.
LED (D02) 1Hz
flashes for approx.
10 seconds on
indoor unit P
.C.
board.
Reboot (Reset)
Outdoor EEPROM error
1.
Outdoor unit power error (V
oltage, noise, etc.)
2.
Outdoor I/F P
.C. board error
Is there any trouble
of outdoor unit
power supply?
Check power voltage and line.
Correct power line.
Check external noise, etc.
Check I/F P
.C. board.
[F24]
Check code
Check code name
Pd sensor error
Cause
Output voltage error of Pd sensor
It is output voltage error of Pd sensor
. Check disconnection of connection of connector (Pd sensor: CN501, red)
circuit and output voltage of sensor
.
If the sensor is normal, replace outdoor I/F P
.C. board.
−
1
9
8
−
Summary of Contents for MMY-MAP0806HT7(J)P
Page 306: ...For HT8 J P E HT8 J P TR model 305 ...
Page 307: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 306 ...
Page 313: ... 312 For HT8 J P E HT8 J P TR model ...
Page 314: ... 313 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 320: ... 319 For HT8 J P E HT8 J P TR model ...
Page 321: ... 320 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 350: ......