Purpose/characteristics
This function allows switching between priority cooling and priority heating.
Four patterns of priority operation mode setting are available as shown in the table below. Select a suitable priority
mode according to the needs of the customer.
Setup
CAUTION
In the case of the priority indoor unit mode, it is necessary to set up the specific indoor unit chosen for priority operation
(a single unit only).
(1) Outdoor unit setup method (header unit)
SW11
Operation
Bit 1
Bit 2
OFF
OFF
Priority heating (factory default)
ON
OFF
Priority cooling
OFF
ON
Priority operation based on No. of units in operation (priority given to the operation mode with the
largest share of units in operation)
ON
ON
Priority indoor unit (priority given to the operation mode of the specific indoor unit set up for priority
operation)
6-
2
-2. Priority Operation Mode Setting
−
9
5
−
Summary of Contents for MMY-MAP0806HT7(J)P
Page 306: ...For HT8 J P E HT8 J P TR model 305 ...
Page 307: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 306 ...
Page 313: ... 312 For HT8 J P E HT8 J P TR model ...
Page 314: ... 313 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 320: ... 319 For HT8 J P E HT8 J P TR model ...
Page 321: ... 320 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 350: ......