Check code
detected by main remote controller)
(
Check code
detected by central control device)
Note: The same error, e.g. a communication error, may result in the display of different check codes depending on the device that detects it.
Moreover, check codes detected by the main remote controller/central control device do not necessarily have a direct impact on air
conditioner operation.
Check code
Display of receiving unit
Typical
problem
site
Description of
problem
Main remote
controller
Outdoor 7-segment display
Indicator light block
Sub-code
Flash
E01
–
–
No master remote controller,
faulty remote controller
communication (reception)
Signals cannot be received from indoor unit;
master remote controller has not been set
(including two remote controller control).
E02
–
–
Faulty remote controller
communication (transmission)
Signals cannot be transmitted to indoor unit.
E09
–
–
Duplicated master remote
controller
Both remote controllers have been set as
master remote controller in two remote
controller control (alarm and shutdown for
header unit and continued operation for
follower unit)
Check code
Display of receiving unit
Typical
problem
site
Description of
problem
TCC-LINK central
control
Outdoor 7-segment display
Indicator light block
Sub-code
Flash
C05
–
–
No indication (when
main remote controller
also in use)
Faulty central control
communication (transmission)
Central control device is unable to transmit
signal due to duplication of central control
device
.
C06
–
–
Faulty central control
communication (reception)
Central control device is unable to receive
signal.
s
r
e
t
p
a
d
a
k
r
o
w
t
e
n
e
l
p
i
t
l
u
M
–
–
–
Multiple network adapters are connected
to remote controller communication line
.
–
–
–
2
1
C
Blanket alarm for general-
purpose device control
interface
Device connected to general-purpose
device control interface for TCC-LINK is
faulty.
P30
–
–
As per alarm unit (see
above)
Group control follower unit
error
Group follower unit is faulty (unit No. and
above detail [
] displayed on main remote
controller)
Operation Timer Ready
Operation Timer Ready
− 16
2
−
Summary of Contents for MMY-MAP0806HT7(J)P
Page 306: ...For HT8 J P E HT8 J P TR model 305 ...
Page 307: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 306 ...
Page 313: ... 312 For HT8 J P E HT8 J P TR model ...
Page 314: ... 313 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 320: ... 319 For HT8 J P E HT8 J P TR model ...
Page 321: ... 320 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 350: ......