7-4-4. Check after Address Setup when Central Control System Is
Connected
When the central control system is connected, check that the following setup has finished after address setup.
NOTE
The figure above does not show all the electric wires.
For details, refer to the installation manuals for the outdoor unit, indoor unit, remote controller, or optional devices.
k
c
e
h
C
s
m
e
t
i
k
c
e
h
c
n
i
a
M
Relay
connector
(1) Is the relay connector of the header unit connected after address setup?
(2)Is the relay connector of the follower unit
disconnect
?
Terminator
resistor
(3)Is the
terminator resistor
(SW30-bit 2) of the header unit with the smallest line address
number
in the central control turned on? (Setup is unnecessary for follower units.)
(4)Is the
terminator resistor
(SW30-bit 2) of the header units, except for the line with the
smallest central control line address, turned off? (Setup is unnecessary for follower units.)
Line address
(5) Are addresses in the line address (SW13, SW14) not duplicated in each refrigerant line?
U1
U2
U1
U2
U1
U2
U1
U2
U1
U2
U5
U6
U3
U4
)
A
(
t
i
n
u
r
e
d
a
e
H
)
A
(
t
i
n
u
r
e
d
a
e
H
U1
U2
U5
U6
U3
U4
U1
U2
U5
U6
A B
A B
A B
A B
(5)
(4)
(5)
)
2
(
)
1
(
(3)
Other refrigerant line
U1
U2
U3
U4
U3
U4
U1
U2
U5
U6
To other refrigerant line
U3
U4
Line address = 1
Line address = 2
Central remote
controller
Follower unit (B)
Follower unit (C)
Outdoor unit
Indoor unit
Remote
controller
Remote
controller
Remote
controller
−
12
6
−
Summary of Contents for MMY-MAP0806HT7(J)P
Page 306: ...For HT8 J P E HT8 J P TR model 305 ...
Page 307: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 306 ...
Page 313: ... 312 For HT8 J P E HT8 J P TR model ...
Page 314: ... 313 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 320: ... 319 For HT8 J P E HT8 J P TR model ...
Page 321: ... 320 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 350: ......