<SW07 Bit 2 OFF (two-step control)>
Power peak-cut control is enabled as long as SW1, as shown on the wiring diagram, is ON (continuously).
Note 1: Specifications of display relay contact
• The terminal for display output ([Operation] terminal) must satisfy the following electrical rating.
When connecting a conductive load (e.g. relay coil) to the display relay load, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
The optional P.C. board should be connected to the header outdoor unit (U1).
Operation
An external power peak-cut control signal limits the peak capacity of the outdoor unit.
L1: Power peak-cut control indication lamp
SW1: Power peak-cut control ON switch*1
SW2: Power peak-cut control OFF switch*1
*1
The inputs of SW1 and SW2 can be either pulse (100 msec or
longer
) or step signals.
* Be sure to provide a contact for each terminal.
Extended power peak-cut control settings
Specifications of display relay contact
Note 1: Specifications of display relay contact
• The terminal for display output ([Operation] terminal) must satisfy the following electrical rating.
When connecting a conductive load (e.g. relay coil) to the display relay load, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
The optional P.C. board should be connected to the header outdoor unit (U1).
Jumper wire
J16
Input
SW1
y
a
l
e
r
r
o
t
a
c
i
d
n
I
1
t
i
B
7
0
W
S
)
1
L
(
N
O
1
t
i
B
F
F
O
1
t
i
B
Cut
OFF
10
0% (
normal operation
)
100
%
(normal operation)
OFF
ON
0% (
forced stop
)
Approx. 60% (upper limit regulated)
ON
<Electrical Rating>
220 to 240 VAC, 10 mA or more, 1 A or less
24 VAC, 10 mA or more, 1 A or less (non-conductive load)
Indication lamp
External power peak-cut control
signals
Peak capacity
I/F SW07 Bit 1
N
O
F
F
O
2
W
S
1
W
S
1
L
OFF
OFF
OFF
100% (normal operation)
100% (normal operation)
ON
ON
OFF
80% (upper limit regulated)
85% (upper limit regulated)
ON
OFF
ON
60% (upper limit regulated)
75% (upper limit regulated)
ON
ON
ON
0% (forced stop)
60% (upper limit regulated)
<Electrical Rating>
220 to 240 VAC, 10 mA or more, 1 A or less
24 VAC, 10 mA or more, 1 A or less (non-conductive load)
PJ17
TB1
[ON]
[OFF]
TB2
COM
ON
COM
OFF
CN513
SW07
Bit 2 ON
L1
SW1
ON
OFF
1 2 3 4
SW2
Connection cable
Locally procured
[OPERATION]
L1: Display lamp
ensuring
power peak cut control
Optional PCB
Header outdoor unit
Shield wire
Shield wire
Outdoor unit
interface PCB
Display
relay
Power
supply
For SW1 and SW2, be sure to provide
no-voltage contacts for each terminal.
6-
2
-
5
. Power peak-cut Control (Extended)
−
9
9
−
Summary of Contents for MMY-MAP0806HT7(J)P
Page 306: ...For HT8 J P E HT8 J P TR model 305 ...
Page 307: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 306 ...
Page 313: ... 312 For HT8 J P E HT8 J P TR model ...
Page 314: ... 313 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 320: ... 319 For HT8 J P E HT8 J P TR model ...
Page 321: ... 320 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 350: ......