Applied Control of Indoor Unit
Control system using remote control interface (TCB-IFCB4E2)
Wiring and setting
• In the case of group control, the control system functions as long as it is connected to one of the indoor units
(control P.C. board) in the group. If it is desired to access the operation and error statuses of other units, relevant
signals must be brought to it from those units individually.
▼
Control items
(1) Start/Stop input signal
Start/stop of unit
(2) In-operation signal
Output present while unit in normal operation
(3) Error signal
Output present while alarm (e.g. serial communication error or operation of protective
device for indoor/outdoor unit) being activated
▼
Wiring diagram of control system using remote control interface (TCB-IFCB4E2)
Input
IFCB4E2: No-voltage ON/OFF serial signal
Output No-voltage
contact (in-operation and error indication)
Contact capacity: Max. AC 240V, 0.5A
1
2
3
4
5
6
1
2
3
4
CN61
T10
(yellow)
1
2
3
4
5
6
CN13
CN06
Indoor control P.C. board
Start/stop input
COM (GND)
Remote controller disabling/enabling input
In-operation signal output
COM (+12V)
Error signal output
Power source 220-240V
ON side
COM
Start signal input
In-operation signal output
Error signal output
OFF side
Stop signal input
TCB-IFCB4E2
−
8
9
−
Summary of Contents for MMY-MAP0806HT7(J)P
Page 306: ...For HT8 J P E HT8 J P TR model 305 ...
Page 307: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 306 ...
Page 313: ... 312 For HT8 J P E HT8 J P TR model ...
Page 314: ... 313 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 320: ... 319 For HT8 J P E HT8 J P TR model ...
Page 321: ... 320 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 350: ......