. Night operation (sound reduction) Control
Operation
This function decreases noise at night or other times as necessary.
The input signal is recognized during its rising/falling phase.
(After reaching the top/bottom of the rising/falling edge, the signal must remain there for at least 100 ms.)
The optional P.C. board should be connected to the header outdoor unit (U1).
The system's capacity is reduced during low-noise operation.
The table below provides a rough guide to this capacity reduction.
* Position of noise measuring device: 1 m from the front face of the set and 1.5 m above ground (anechoic sound)
Terminal
Input signal
Operation
COOL
(SW1)
Night time control
Normal operation
Relative to maximum capacity
SW1: Night time signal switch
7
1
J
P
8
0
5
N
C
TB1
SW1
COM
HEAT
COOL
Locally procured
Optional PCB
Header outdoor unit
Outdoor unit
interface PCB
Connection
cable
Shield
wire
ON
OFF
ON
OFF
−
10
1
−
Model
MMY-
Cooling
Heating
50
MAP0806*
approx. 85%
50
approx. 80%
MAP1006*
approx. 70%
50
approx. 65%
MAP1206*
approx. 60%
53
approx. 55%
MAP1406*
approx. 80%
approx. 80%
Capacity
During low-noise mode*
dB(A)
MAP14B6*
50
approx. 50%
−
MAP10A6*
53
approx. 90%
approx. 90%
MAP12A6*
53
approx. 85%
approx. 85%
53
MAP1606*
approx. 70%
approx. 70%
53
MAP18B6*
approx. 60%
−
MAP14A6*
54
approx. 75%
approx. 75%
MAP16A6*
54
approx. 70%
approx. 70%
MAP1806*
54
approx. 65%
approx. 65%
MAP2006*
54
approx. 60%
approx. 60%
MAP2206*
54
approx. 55%
approx. 55%
Summary of Contents for MMY-MAP0806HT7(J)P
Page 306: ...For HT8 J P E HT8 J P TR model 305 ...
Page 307: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 306 ...
Page 313: ... 312 For HT8 J P E HT8 J P TR model ...
Page 314: ... 313 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 320: ... 319 For HT8 J P E HT8 J P TR model ...
Page 321: ... 320 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 350: ......