This function is provided to open or close forcedly PMV for 2 minutes in all the indoor units by the switch operation
on the interface P.C. board of the header unit.
This function is also used to open PMV fully when turning off the power and executing an operation.
<Operation>
[Open fully]
Set the switches SW01/SW02/SW03 on the interface P.C. board of the header unit to [2/3/1], and press SW04 for
2 seconds or more.
(Display appears on 7-segment display for 2 minutes as follows.) [P ] [ FF]
[Close fully]
Set the switches SW01/SW02/SW03 on the interface P.C. board of the header unit to [2/3/1], and press SW05 for
2 seconds or more.
(Display appears on 7-segment display for one minute as follows.) [P ] [ 00]
[Clear]
After 2 minutes (1 minutes for “Close fully”) after setting up, the opening automatically returns to the normal
opening.
This function is provided to forcedly open or close fully P.M.V. (PMV1/PMV
3
, PMV4) used in the outdoor unit for 2
minutes.
[PMV1 Open fully]
On the interface board of the outdoor unit, set the
DIP
switch [SW12·bit1] to [OFF], [SW12·bit2] to [OFF], and
short-circuit CN30.
[PMV1 Close fully]
On the interface board of the outdoor unit, set the
DIP
switch [SW12·bit1] to [OFF], [SW12·bit2] to [OFF], and
short-circuit CN31.
[PMV
3
Open fully]
On the interface P.C. board of the outdoor unit, set the
DIP
switch [SW12·bit1] to [ON], [SW12·bit2] to
[OFF],
and shortcircuit CN30.
[PMV
3
Close fully]
On the interface P.C. board of the outdoor unit, set the
DIP
switch [SW12·bit1] to [ON], [SW12·bit2] to
[OFF],
and shortcircuit CN31.
[Clear]
For both open fully and close fully, after 2 minutes, the opening returns to the normal opening.
Be sure to remove the cord used for short-circuit after confirmation, and set the
DIP
switch [SW12·bit1] to
[OFF] and [SW12·bit2] to [OFF].
7-7-5. Pulse Motor Valve (PMV) Forced Open/Close Function in Indoor
Unit
7-7-6. Pulse Motor Valve (PMV) Forced Open Fully/Close fully
Function in Outdoor Unit
[PMV4 Open fully]
On the interface board of the outdoor unit, set the
DIP
switch [SW12·bit1] to [OFF], [SW12·bit2] to [ON], and
short-circuit CN30.
[PMV4 Close fully]
On the interface board of the outdoor unit, set the
DIP
switch [SW12·bit1] to [OFF], [SW12·bit2] to [ON], and
short-circuit CN31.
−
1
4
7
−
Summary of Contents for MMY-MAP0806HT7(J)P
Page 306: ...For HT8 J P E HT8 J P TR model 305 ...
Page 307: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 306 ...
Page 313: ... 312 For HT8 J P E HT8 J P TR model ...
Page 314: ... 313 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 320: ... 319 For HT8 J P E HT8 J P TR model ...
Page 321: ... 320 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 350: ......