13-1-8. Noise Filter P.C. Board (MCC-1608A, B) Replacement Procedure
<
MAP0806
∗
, 1006
∗
, 1206
∗
, 14B6
∗
, 10A6
∗
, 12A6
∗
, 1406
∗
, 1606
∗
, 18B6
∗
type
>
Replacement steps:
(1)
Turn off the power supply of the outdoor unit and allow at least 3 minutes for the capacitor to discharge.
(2) Remove the terminal block sub-assembly
①
.
Remove the screws
②
on the power supply terminal block
④
and the screws
③
securing the terminal block
subassembly
①
.
• he screws will be reused during the installation of the service P.C. board, so keep them in a safe place.
(3) Disconnect all the connectors and Faston terminals used to connect wiring to the noise filter P.C. board.
• he line filter
⑨
and its leads, both connected to the screw-on terminals
⑧
of the noise filter P.C. board (A) will
be removed in step 6.
• D sconnect all the connectors and Faston terminals.
Ex.
MMY-MAP1206HT8P
Noise Filter P.C. board
(MCC-1608)
Noise Filter P.C. board
(43T6V623)
PCB Mount
⑦
⑦
⑦
Screw
⑤
⑧
Screw-on
terminal
⑧
⑧
⑧
⑧
⑧
Noise Filter
P.C. board (A)
(MCC-1608A)
Noise Filter
P.C. board B
(MCC-1608B)
⑦
Line Filter
⑨
Remove terminal block
sub-assembly
①
②
Screw
③
Screw
④
Power supply
terminal block
③
③
Screw
⑥
PCB Mount
⑩
⑦
⑦
②
②
③
⑩
⑩
②
−
2
9
7
−
Summary of Contents for MMY-MAP0806HT7(J)P
Page 306: ...For HT8 J P E HT8 J P TR model 305 ...
Page 307: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 306 ...
Page 313: ... 312 For HT8 J P E HT8 J P TR model ...
Page 314: ... 313 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 320: ... 319 For HT8 J P E HT8 J P TR model ...
Page 321: ... 320 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Page 350: ......