11
4
Parts Specifications
Outdoor Units
COMPRESSOR
MODEL
MM-A0280HT MM-A0224HT
MM-A0280HX MM-A0224HX MM-A0160HX
Model Name
MG1450CW-21B
YG1800CW-B1
YG1700CW-B1
YG890C-B1
Motor Type
3 – Phase induction motor
Power Supply
380 – 415V, 3 – Phase, 50Hz
Output
(k
Ω
)
7.5
7.5
7.5
7.5
4.1
Pole
(P)
2/2 (INV/Fixed)
2/2 (Fixed/Fixed)
2
Coil Resistance (W)
1.18/2.25 (INV/Fixed)
2.25/2.25 (Fixed/Fixed)
2.250
Comp. Oil Name
NISSEKI RB68AF VG 74
Amount of Oil (ml)
7500
7500
7500
7500
2000
Inner Over-load Relay
Opens: 115±5 °C Closes: 93±10°C
PARTS NAME
SPECIFICATION
Model Name
STF-200-350A
Motor Type
1-Phase induction motor
Fan Motor
Power Supply
AC 220-240V, 1 Phase, 50Hz
Output (W)
400
Current (A)
4.81~5.89
Pole (P)
6
High Pressure Switch
Model Name
INV=ACB-JB128 FIX=ACB-JA64
Operating Pressure (kgf/cm
2
G)
Operation: 3.2, Reset 2.55
High Pressure Sensor
Model Name
150NH4-H
Operating Conditions
0~3.33MPa
Low Pressure Sensor
Model Name
150NH4-L
Operating Conditions
0~0.98MPa
Compressor Case Heater
AC240V, 74W
Accumulator Case Heater
AC240V, 29W
Discharge Temperature Sensor
At 50ºC=18.1K
Ω
, At 100ºC=3.35K
Ω
W,
Suction Temperature Sensor
At 0ºC=34.6K
Ω
, At 25ºC=10.0K
Ω
, At 50ºC=3.4K
Ω
Pulse Modulating Valve
L12A-03, DC12V
Pulse Modulating Valve (For Cooling Bypass)
A12A-15, DC12V
2-way Valve
VPV-603D, Coil 240V
2-way Valve
NEV-202D, Coil 240V
4-WAY VALVE
MODEL
MM-A0280HT MM-A0224HT
MM-A0280HX MM-A0224HX MM-A0160HX
Model Name
CHV-0712
CHV-0712
CHV-0712
CHV-0712
CHV-0401
Coil Specification
AC240V
AC240V
AC240V
AC240V
AC240V
MM-A0280HT, MM-A0224HT, MM-A0280HX, MM-A0224HX, MM-A0160HX
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...