66
14
Troubleshooting
Diagnostic Procedure for Check Code
66
Check code
Operation cause
1. Pd sensor error
2. Service valve closed
3. Outdoor fan, capacitor error
[22]
4. Indoor/Outdoor PMV blockage
High-pressure protective operation
5. Outdoor heat exchanger blockage
6. SV2 circuit blockage
7. Communication error between indoor and
outdoor units
Is the high-pressure sensor
characteristics normal
?
Are the connections for the
capacitor and fan motor normal
?
Is service valve fully open
?
Does the outdoor fan operate
?
Refrigerant over charge
Blockage
Pipe breakage
Abnormal overload
Remove cause.
Open service valve fully.
Check outdoor interface P.C. board.
If defective, replace.
Repair defective part.
Repair SV2 bypass circuit.
(Coil error, disconnection of
wiring etc.)
No
Yes
No
Yes
No
Yes
No
Yes
Is there a problem with the
outdoor unit heat exchanger
?
➀
Blockage of heat exchanger
➁
Short circuit
Yes
No
Is SV2 bypass circuit normal
?
No
Yes
Check parts.
If defective, replace.