Self Diagnostic Display Information
Outdoor Units
SW03 SW02 SW01
Displayed content
1 to 3 1 to 16
4
Indoor communication/
A
[01] to [48]: Indoor address number
Receive status
B
[ 1]: Receiving, [– –]: No connection
5
Indoor check code
A
[01] to [48]: Indoor address number
B
[– –]: No error, a check code is displayed when an error
occurs.
6
Indoor horse power
A A [01] to [48]: Indoor address number
B
Corresponded HP is displayed. ([– –]: No connection)
[0, 8], [ 1], [1, 2], [1, 5], [1, 7], [ 2]
[2, 5], [ 3], [3, 2], [ 4], [ 5]
7
Indoor demand
A
[01] to [48]: Indoor address number
command (S code)
B
[ 0]: In STOP time, [ 3] to [ F]: During operation (S3 to SF)
8
Indoor PMV opening
A
[01] to [48]: Indoor address number
B
Data is displayed as pulse
9
Indoor saturation temp.
A
[01] to [48]: Indoor address number
B
Data is displayed as temperature
10
Indoor TA sensor
A
[01] to [48]: Indoor address number
B
Data is displayed as temperature
11
Indoor TC2 sensor
A
[01] to [48]: Indoor address number
B
Data is displayed as temperature
12
Indoor TC1 sensor
A
[01] to [48]: Indoor address number
B
Data is displayed as temperature
(5) Outdoor unit information data display (Displayed on inverter unit only)
SW03
SW02
Outdoor unit number
7 segment display A
1
1 to 16
SW02 setup number
[01] to [16]
2
1 to 16
SW02 setup 16
[17] to [32]
3
1 to 16
SW02 setup 32
[33] to [48]
NOTE:
The indoor address number is set by selecting SW02 or SW03.
• 7 segment display A, B
Display A
Display B
D716
D717
D714
D715
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...