Troubleshooting
Diagnostic Procedure for Check Code
Is the wiring connection
to the communication cable
(PQ) normal
?
Is the communication cable
connected to another
outdoor unit incorrectly
?
Is the communication cable
connected to the central
management remote controller
?
No
Yes
Yes
No
No
Yes
No
Yes
Modify communication cable.
Modify wiring of wire connector.
Is the No. of indoor units connected
to the outdoor unit normal
?
Check interface P.C. board
of outdoor unit.
If defective, replace.
Check code
Operation cause
1. Connection error of communication cable (PQ)
[96]
between indoor and outdoor units
Consistency detection of indoor
2. Abnormal No. of connected indoor units
and outdoor addresses
3. Wiring connection error of central management
remote controller