Introduction
Components
5
1
Inverter unit
Fixed-speed unit
Appearance
Corresponding HP
8HP
10HP
6HP
8HP
10HP
Model name
MM-A0224HT MM-A0280HT MM-A0160HX MM-A0224HX MM-A0280HX
Cooling capacity (kW)
22.4
28.0
16.0
22.4
28.0
Heating capacity (kW)
25.0
31.5
18.0
25.0
31.5
Corresponding HP
8HP
10HP 14HP
16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP
38HP 40HP 42HP 44HP 46HP
Combined Model MM-A~HT 0224 0280 0384
0440 0504 0560 0608 0672
0728 0784 0840 0896 0952 1008
1064 1120 1176
1232 1288
Cooling capacity (kW)
22.4
28.0
38.4
44.8
50.4
56.0
60.8
67.2
72.8
78.4
84.0
89.6
95.2 100.8 106.4 112.0 117.6 123.2 128.8
Inverter unit
8HP
10HP
8HP
8HP 10HP 10HP
8HP
8HP
10HP 10HP 10HP
8HP
10HP 10HP
10HP 10HP 10HP 10HP 10HP
—
—
6HP
8HP
8HP
10HP
8HP
8HP
8HP
10HP 10HP
8HP
8HP
10HP
10HP 10HP
8HP
10HP 10HP
—
—
—
—
—
—
6HP
8HP
8HP
8HP
10HP
8HP
8HP
8HP
10HP 10HP 8HP
8HP 10HP
—
—
—
—
—
—
—
—
—
—
—
8HP
8HP
8HP
8HP
10HP 8HP
8HP
8HP
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
8HP
8HP
8HP
13
16
16
18
18
20
22
24
26
28
30
32
34
36
38
40
40
40
40
Min. HP Connected
4
5
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Max. HP Connected
10.8
13.5
18.9
21.6
24.3
27
29.7
32.4
35.1
37.8
40.5
43.2
45.9
48.6
51.3
54
56.7
59.4
62.1
Combined
outdoor
units
No. of connectable
indoor units
Fixed-
speed unit
1. Outdoor Unit
2. Outdoor Units (Combination of Outdoor Units)
(*1). Code is determined according to the capacity code of the indoor units connected.
(*2). If the total capacity code value of indoor units exceeds that of outdoor units, apply the
capacity code of outdoor units.
(*3). When using a branch header, indoor units with a maximum of 6.0 capacity code in total
can be connected to each branch.
NOTE:
If the length of the gas pipe exceeds 30m from the 1st branching to an indoor unit,
increase the gas pipe size by 1 size, i.e. MM-U140 = Gas Ø22.2, Liquid Ø9.5
Model name
Usage
Appearance
RBM-Y018
Indoor unit capacity code (*1): Total below 6.4
Y-shape branching joint
RBM-Y037
Indoor unit capacity code (*1): Total 6.4 or more and below 13.2
(*2)
RBM-Y071
Indoor unit capacity code (*1): Total 13.2 or more and below 25.2
(*2)
RBM-Y129
Indoor unit capacity code (*1): Total 25.2 or more
(*2)
4-branching header (*3)
RBM-H4037
Indoor unit capacity code (*1): Total below 13.2
Max. 4
RBM-H4071
Indoor unit capacity code (*1): Total 13.2 or more and below 25.2
branches
8-branching header (*3)
RBM-H8037
Indoor unit capacity code (*1): Total below 13.2
Max. 8
RBM-H8071
Indoor unit capacity code (*1): Total 13.2 or more and below 25.2
branches
1 set of 3 types of T-shape joint pipes as described below:
The required quantity is arranged and they are combined at the site.
T-shape branching joint
(For connection of
RBM-T129
outdoor unit)
Connecting pipe
Corresponding dia. (mm).
Qty
Balancing pipe
Ø9.52
1
Piping at liquid side
Ø12.7 to Ø22.2
1
Piping at gas side
Ø22.2 to Ø54.1
1
3. Branching joints/headers
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...