Troubleshooting
Diagnostic Procedure for Check Code
88
14
Check code
Operation cause
[d8]
TK1 sensor out of place, miswiring, resistance
TK1 temperature detection
value characteristics error
circuit alarm
Is TK1 sensor out of place
?
Is there miswiring of
TK1/TK2/TK3 sensor
?
Modify miswiring.
TK1 sensor: CN516
TK2 sensor: CN515
TK3 sensor: CN507
Sensor error.
Modify sensor mounting.
No
Yes
Yes
No
Is resistance value
characteristics of TK1 sensor
normal
?
Yes
No
Check interface P.C. board.
[
]
( *1) 2-way valve leakage/blockage check procedure
1. After resetting the power supply, start a trial operation.
2. Set SW01/SW02/SW03 on interface P.C. board to
1/16/1, respectively.
3. Check the 7 segment display of the interface P.C. board.
In case of judgment result “A0”
Oil level is adequate. Resume the operation.
In case of judgment result “A1”
Oil level is insufficient. Check the following items.
Remove SV3C valve coil, reset the
power supply, and start the trial operation.
4. After operation for several minutes, check
temperature at secondary side of SV3C
valve (A).
When temperature is high (Equivalent
to discharge temp.), leakage occurs
from SV3C valve.
Replace SV3C coil.
5. Remove SV3A coil, and start a
trial operation under condition that
AC220V–240V-power is on and SV3C valve
is connected.
6. After operation for several minutes, check
temperature at secondary side of SV3A
valve (B).
When temperature is high (equivalent to discharge temp.), leakage occurs from
SV3A valve.
Replace SV3A coil.
7. Using charge hose, etc., connect the check joint of gas pipe (D) and the charge port of
balancing pipe.
8. Start a trial operation under condition that AC220V–240V-power is and to SV3B valve is
connected.
9. After operation for several minutes, check temperature at secondary side of SV3B valve (C).
When temperature is low (equivalent to suction temp.), blockage occurs in SV3B valve
or strainer.
Replace blocked part.
( *2) Blockage check procedure for oil return circuit of oil separator
1. Check temperature of oil circuit during operation of outdoor unit.
If temperature is low, clogging occurs in capillary or strainer.
Replace blocked part.
TK1 sensor
TK2
sensor
(A)
(B)
(C)
Valve
strainer
Oil
separator
(D)
Check joint
Strainer
Capillary
Strainer
Strainer
Strainer
Check
joint
Capillary
Accumulator
Compressor
Balancing pipe valve
SV3C
SV3A
valve
SV3B
valve
Check
valve
Oil
removal
valve
Check
valve
Check
valve
Oil
tank
7 segment display
When operation has started
"OL" "– –"
During detection of oil level
"OL" "FF" or "Numeral"
Judgement result of oil level "OL" "AO" or "A1"
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...