59
14
Troubleshooting
Diagnostic Procedure for Check Code
Check code
Operation cause
1. Float switch disconnection
[0b]
2. Drain pump operation error
Indoor water overflow alarm
3. Drain hose blockage
Check code
Operation cause
[0C] Indoor TA sensor alarm
TA sensor open/short
Is drain pump connected
?
Is circuit wiring normal
?
(*1)
Is power to drain pump
turned on
?
(*2)
Does float switch operate
?
Does drainage water collect
?
Does drain pump operate
?
Check for blockage of
drainage hose.
Check connection of connector CN11
(Drain pump: Indoor main,
P.C. board (MCC-1361-01))
Check and modify wiring circuit.
(MCC-1361-01)
Indoor P.C. board error
(MCC-1361-01)
Float switch error
Check and modify wiring circuit.
Drain pump error.
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Yes
(*1) For confirmation, check voltage under
condition that connector is connected to CN11.
(*2) Check whether voltage of
CN08, pins 1 to 3 of the
indoor main P.C. board, is
230V or not (MCC1361-01).
TA sensor open/short has been detected. Check disconnection of connector connection
(TA sensor: CN04) circuit and resistance value characteristics of sensor.
When the sensors are normal, replace indoor P.C. board (MCC-1361-01).
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...