47
12
Self Diagnostic Display Information
Outdoor Units
Outdoor unit information data display (Displayed on each outdoor unit)
SW03 SW02 SW01
Displayed content
1
1
1
Check code
A
[U1] to [U5]: Outdoor unit number (1: Inverter)
B
[– –]: Normal time (No error),
a check code is displayed in abnormality.
<SW04> Push function:
Only fan of unit in which an error occurred operates.
<SW04 + SW05> Push function: Only fan of normal unit operates.
<SW05> Push function: Fan operation function is interrupted.
2
Type of installed
A
[U1] to [U2]: Outdoor unit number
compressor
B
[ A]: Fixed-speed 2 in 1, [ b]: Fixed-speed 2 compressor
[ C]: Fixed-speed single, [ d]: Inverter (2 in 1)
3
Operation mode
A —
B
[ C]: Cooling operation, [ H]: Heating operation
4
Outdoor unit capacity
A
[ 6], [ 8], [10]: 6, 8, 10HP
B
[HP]
5
Compressor operation
A
[1. –]: No.1 compressor stop status, [1. 1]: During operation
command
For inverter, the frequency code is displayed: [00] to [FF]
B
[2. –]: No.2 compressor stop status, [2. 1]: During operation
<SW04> Push function:
Inverter frequency data is displayed in decimal notation.
<SW05> Push function:
Release of frequency data display in decimal notation
6
Outdoor fan operation
A
[FP]
pattern
B
[ 0] to [16]: 0 wave (stop) to 16 waves (All waves)
7
Compressor backup
A
[C1]: Under No.1 compressor backup setup
B
[C2]: Under No.2 compressor backup setup
8
—
A
—
B
—
9
Control valve output
A
B
SV2: OFF
H. O
2.
0
SV2: ON
H. O
2.
1
10
SV3A: ON/SV3B: OFF/SV3C: OFF
3. 1
0
0
SV3A: OFF/SV3B: ON/SV3C: OFF
3. 0
1
0
SV3A: OFF/SV3B: OFF/SV3C: ON
3. 0
0
1
11
SV41: ON/SV42: OFF
4. 0
1
0
SV41: OFF/SV42: ON
4. 0
0
1
12
—
—
—
13
—
—
—
14
PMV A1 + PMV A2 opening
[ 00] to [500]: 0 to 1000 pulse
0
0
P
15
PMVB opening
[ 00] to [500]: 0 to 500 pulse
0
0
P
16
Oil level judgment status
A
[OL]
B
[ ]: Initial display, [FF]: Oil judgment start status
[A0]: Adequate, [A1]: Shortage, [A2 to A4]: Detection error
<SW04> Push function:
Oil level judgment control forcible start
(Detection starts after timer count down)
<SW05> Push function:
Oil level shortage status/Continuous counter display
(Displayed for several seconds)
NOTE:
The push-switch function operates by input from the inverter unit.
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...