Troubleshooting
Diagnostic Procedure for Check Code
Check code
Operation cause
[E6]
1. Power supply error
Fixed-speed IOL,
2. Fixed-speed compressor IOL operation
OL system alarm (1)
3. Service valve closed
[F1]
4. Blockage in indoor/outdoor PMV
Fixed-speed IOL,
5. Miswiring of communication between indoor and
OL system alarm (2)
outdoor units
Does OCR operate
?
Check the OCR reset button.
(Manual reset)
Is constant speed
compressor normal
?
1. Is compressor winding
normal
?
2. Is compressor locked
?
Is OCR circuit normal
?
1.OCR unit
2.OCR wiring
Repair power supply.
Open valves fully.
Repair OCR circuit.
Replace Mg-SW.
Replace fixed-speed
compressor.
Overload operation,
liquid compression
Check the following:
1. Power supply voltage
is 380/400/415V
2. Phase missing, short-
circuit of fixed-speed
compressor power
supply
Yes
No
No
Yes
No
Yes
Yes
No
Is Mg-SW faulty
?
[E6]: IOL operation circuit error compressor 1 side
[F1]: IOL operation circuit error compressor 2 side
Yes
No
Yes
Is IOL circuit normal
?
1.Connector
2.Wiring
3.Outdoor P.C. board
Is the cooling bypass
PMV B normal
?
Is wiring normal
?
Repair IOL circuit.
Cooling bypass PMV B error
Correct wiring.
No
Yes
Are gas pipe, liquid pipe,
and service valve of the
outdoor unit fully open
?
No
No
Yes
No
Yes
Insufficient refrigerant,
blockage, pipe breakage.
(Check miswiring of the outdoor unit according to miswiring check function.)
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...