Troubleshooting
Diagnostic Procedure for Check Code
67
Is the system backup of the
outdoor unit being completed
?
Is the No.of connected
indoor units acceptable
?
(*2)
Is the HP setting correct for each
individual indoor unit
?
No
Yes
No
Yes
No
Yes
No
Yes
Indoor unit over capacity was
detected during outdoor unit system
setup. Setup “no detection” of over
capacity (*1).
Confirm system specification.
Correct HP setting.
Keep capacity of connected indoor
units within 135%.
Is the total capacity of connected
indoor units within 135%
?
Check inverter P.C. board.
Check code
Operation cause
[89]
1. No. of connected indoor units/connected over
Indoor over capacity
capacity.
2. Incorrect setup of indoor unit HP.
Check code
Operation cause
[87]
Missing phase of outdoor unit power source
Missing phase
A Phase of the outdoor unit power source is missing.
Modify the power source wiring.
( *1) Setup “no detection” of over capacity.
Turn on SW09 bit 2 on interface P.C. board of outdoor unit (usually OFF).
( *2) Check No. of connected indoor units.
Set SW01/SW02/SW03 on interface P.C. board of outdoor unit to 1/4/3, respectively.
No. of connected units is displayed on the 7 segment display.