261
⎯
6
F
2
S
0
8
3
5
Binary Output Default Setting List (4)
Relay Model Module
BO No.
Terminal No.
Signal Name
Contents
Setting
Name
Signal
No.
LOGIC
(OR:1, AND:2)
TIMER
(OFF:0, ON:1)
GRL100
-204
IO#2
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
TB3:
A2-A1
A2-B1
A2-B2
A3-B3
A4-B4
A5-B5
A6-B6
A7-B7
A8-B8
A9-B9
A10-B10
A11-B11
A13-B13
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-A1
TRIP-B1
TRIP-C1
ARC1
COMM1_FAIL
85R1.REM1
85R2.REM1
Trip A phase
Trip B phase
Trip C phase
Trip A phase
Trip B phase
Trip C phase
Trip A phase
Trip B phase
Trip C phase
Autoreclose
Communication failure
Transfer trip 1 receive
Transfer trip 2 receive
99
100
101
99
100
101
99
100
101
177
225
197
198
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
1
1
1
(FAIL) A12-B12
RELAY
FAILURE
--
--
--
--
IO#3
BO1
BO2
BO3
BO4
BO5
BO6
TB2:
A1-B1
A2-B2
A3-B3
A4-B4
A5-B5
A6-B6
TRIP-A1
TRIP-B1
TRIP-C1
DIF-
∗
/DIFG_TRIP
OST_TRIP
CBFDET
Trip A phase
Trip B phase
Trip C phase
DIF, DIFG relay operating
OST trip
CBF detection
99
100
101
82, 83, 84, 86
87
91
1
1
1
1
1
1
1
1
1
1
1
1
GRL100
-206
IO#2
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
TB2:
A2-A1
A2-B1
A2-B2
A3-B3
A4-B4
A5-B5
A6-B6
A7-B7
A8-B8
A9-B9
A10-B10
A11-B11
A13-B13
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-A1
TRIP-B1
TRIP-C1
ARC1
COMM1_FAIL
85R1.REM1
85R2.REM1
Trip A phase
Trip B phase
Trip C phase
Trip A phase
Trip B phase
Trip C phase
Trip A phase
Trip B phase
Trip C phase
Autoreclose
Communication failure
Transfer trip 1 receive
Transfer trip 2 receive
99
100
101
99
100
101
99
100
101
177
225
197
198
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
1
1
1
(FAIL) A12-B12
RELAY
FAILURE
--
--
--
--
IO#4
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
BO14
TB3:
A2-A1
A2-B1
A2-B2
A3-B3
A4-B4
A5-B5
A6-B6
A7-B7
A8-B8
A9-B9
A10-B10
A11-B11
A12-B12
A13-B13
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-A1, -B1, -C1
TRIP-A1, -B1, -C1
Trip A phase
Trip B phase
Trip C phase
Trip A phase
Trip B phase
Trip C phase
Trip A phase
Trip B phase
Trip C phase
Trip A phase
Trip B phase
Trip C phase
Trip A, B or C phase
Trip A, B or C phase
99
100
101
99
100
101
99
100
101
99
100
101
99, 100, 101
99, 100, 101
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
IO#3
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
TB5:
A1-B1
A2-B2
A3-B3
A4-B4
A5-B5
A6-B6
A7-B7
A8-B8
A9-B9
A10-B10
TRIP-A1
TRIP-B1
TRIP-C1
DIF-A, -B, -C_TRIP
DIFG_TRIP
OST_TRIP
CBFDET
SPAR1
TPAR1
MPAR
Trip A phase
Trip B phase
Trip C phase
DIF relay operating
DIFG relay operating
OST trip
CBF detection
Single pole autoreclose
Three pole autoreclose
Multi-pole autoreclose
99
100
101
82, 83, 84
86
87
91
173
175
183
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Summary of Contents for GRL100-101A
Page 223: ... 222 6 F 2 S 0 8 3 5 ...
Page 228: ... 227 6 F 2 S 0 8 3 5 Appendix B Signal List ...
Page 256: ... 255 6 F 2 S 0 8 3 5 Appendix C Variable Timer List ...
Page 258: ... 257 6 F 2 S 0 8 3 5 Appendix D Binary Output Default Setting List ...
Page 269: ... 268 6 F 2 S 0 8 3 5 ...
Page 270: ... 269 6 F 2 S 0 8 3 5 Appendix E Details of Relay Menu ...
Page 279: ... 278 6 F 2 S 0 8 3 5 ...
Page 288: ... 287 6 F 2 S 0 8 3 5 Appendix G Typical External Connection ...
Page 326: ... 325 6 F 2 S 0 8 3 5 Appendix J Return Repair Form ...
Page 330: ... 329 6 F 2 S 0 8 3 5 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 331: ... 330 6 F 2 S 0 8 3 5 ...
Page 332: ... 331 6 F 2 S 0 8 3 5 Appendix K Technical Data ...
Page 343: ... 342 6 F 2 S 0 8 3 5 ...
Page 344: ... 343 6 F 2 S 0 8 3 5 Appendix L Symbols Used in Scheme Logic ...
Page 347: ... 346 6 F 2 S 0 8 3 5 ...
Page 348: ... 347 6 F 2 S 0 8 3 5 Appendix M Multi phase Autoreclose ...
Page 351: ... 350 6 F 2 S 0 8 3 5 ...
Page 352: ... 351 6 F 2 S 0 8 3 5 Appendix N Data Transmission Format ...
Page 358: ... 357 6 F 2 S 0 8 3 5 Appendix O Example of DIF and DIFG Setting ...
Page 364: ... 363 6 F 2 S 0 8 3 5 Appendix Q IEC60870 5 103 Interoperability ...
Page 377: ... 376 6 F 2 S 0 8 3 5 ...
Page 378: ... 377 6 F 2 S 0 8 3 5 Appendix R Failed Module Tracing and Replacement ...
Page 384: ... 383 6 F 2 S 0 8 3 5 Appendix S PLC Setting Sample ...
Page 386: ... 385 6 F 2 S 0 8 3 5 Appendix T Ordering ...
Page 392: ......