Element Range
Step
Default
Remarks
Communication
Mode
A
B
GPS
DIF
Phase
current
DIFI1
0.50
−
10.00A
0.01A
5.00A
Small current region
x
x
x
(0.10
−
2.00A
0.01A
1.00A)(*1)
DIFI2
3.0
−
120.0A
0.1A
15.0A
Large current region
x
x
x
(0.6
−
24.0A
0.1A 3.0A)
DIFG DIFGI
0.25
−
5.00A
0.01A 2.50A
Residual
current
x x x
(0.05
−
1.00A
0.01A 0.50A)
DIFIC
0.00
−
5.00A
0.01A 0.00
A
x x x
(0.00
−
1.00A
0.01A 0.00
A)
Charging current compensation
Vn
100 - 120V
1V
110V
Rated line voltage
x
x
x
TDIFG 0.00
−
10.00s
0.01s
0.50s
Delayed tripping timer
x
x
x
DIFSV 0.25
−
10.00A
0.01A 0.50A
x x x
(0.05
−
2.00A
0.01A 0.10A)
Differential current (Id) monitoring
TIDSV
0 – 60s
1s
10s
Timer for Id detection
x
x
x
OCCHK (*5)
0.5
−
5.0A
0.1A 0.5A
-- -- x
(0.10
−
1.00A
0.01A 0.10A)
Minimum current for phase difference
check
HYS
θ
(*5)
1
−
5 deg
1 deg
1 deg
Phase difference check margin
--
--
x
TDSV
100 - 16000
1
μ
s 6000
μ
s
Transmission delay time threshold
setting for alarm (*8)
x x x
TCDT1
−
10000
−
10000
1
μ
s 0
μ
s
Transmission delay time difference
setting for channel 1 (*7)
x x x
TCDT2
−
10000
−
10000
1
μ
s 0
μ
s
Transmission delay time difference
setting for channel 2 (*7)
x x x
PDTD
200 - 2000
μ
s 1
μ
s 1000
μ
s
Transmission delay time difference
between send and receive channels
(GPS synchronization only)
-- -- x
RYID
0-63
0
Local relay address
-- x x
RYID1
0-63
0
Remote 1 relay address
-- x x
RYID2
0-63
0
Remote 2 relay address
-- x x
[DIFG]
ON/OFF
ON
High impedance earth fault protection
x
x
x
[STUB] ON/OFF ON
or
OFF(*2)
Measure for stub fault
x
x
x
[RDIF]
ON/OFF
ON
Remote differential protection
--
x
x
[T.F.C]
ON/OFF
OFF
Measure for through fault current
x
--
--
[OTD]
ON/OFF
OFF
Open terminal detection
x
x
x
[DIF-FS]
OFF / OC / OCD /
Both
OFF Fail-safe
function
x
x
x
[DIFG-FS] ON/OFF
OFF Fail-safe
function
x x x
[COMMODE]
A / B / GPS
B
Communication mode
A
B
GPS
[TERM] 2TERM/3TERM
/Dual (*3)
3TERM
For three-terminal application models
x
x
x
[SP.SYN] Master/Slave Master(*4) Sampling synchronization
x
x
x
[CH. CON]
Normal/Exchange
Normal
Telecommunication port exchanger
x
x
x
Summary of Contents for GRL100-101A
Page 223: ... 222 6 F 2 S 0 8 3 5 ...
Page 228: ... 227 6 F 2 S 0 8 3 5 Appendix B Signal List ...
Page 256: ... 255 6 F 2 S 0 8 3 5 Appendix C Variable Timer List ...
Page 258: ... 257 6 F 2 S 0 8 3 5 Appendix D Binary Output Default Setting List ...
Page 269: ... 268 6 F 2 S 0 8 3 5 ...
Page 270: ... 269 6 F 2 S 0 8 3 5 Appendix E Details of Relay Menu ...
Page 279: ... 278 6 F 2 S 0 8 3 5 ...
Page 288: ... 287 6 F 2 S 0 8 3 5 Appendix G Typical External Connection ...
Page 326: ... 325 6 F 2 S 0 8 3 5 Appendix J Return Repair Form ...
Page 330: ... 329 6 F 2 S 0 8 3 5 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 331: ... 330 6 F 2 S 0 8 3 5 ...
Page 332: ... 331 6 F 2 S 0 8 3 5 Appendix K Technical Data ...
Page 343: ... 342 6 F 2 S 0 8 3 5 ...
Page 344: ... 343 6 F 2 S 0 8 3 5 Appendix L Symbols Used in Scheme Logic ...
Page 347: ... 346 6 F 2 S 0 8 3 5 ...
Page 348: ... 347 6 F 2 S 0 8 3 5 Appendix M Multi phase Autoreclose ...
Page 351: ... 350 6 F 2 S 0 8 3 5 ...
Page 352: ... 351 6 F 2 S 0 8 3 5 Appendix N Data Transmission Format ...
Page 358: ... 357 6 F 2 S 0 8 3 5 Appendix O Example of DIF and DIFG Setting ...
Page 364: ... 363 6 F 2 S 0 8 3 5 Appendix Q IEC60870 5 103 Interoperability ...
Page 377: ... 376 6 F 2 S 0 8 3 5 ...
Page 378: ... 377 6 F 2 S 0 8 3 5 Appendix R Failed Module Tracing and Replacement ...
Page 384: ... 383 6 F 2 S 0 8 3 5 Appendix S PLC Setting Sample ...
Page 386: ... 385 6 F 2 S 0 8 3 5 Appendix T Ordering ...
Page 392: ......