Troubleshooting
No.
Phenomena
Supposed causes
Check / Confirmation
Object
Procedure
Address setting is incorrect.
BCU
RY
Match address setting between BCU and relay.
Avoid duplication of address with other relay.
Transmission baud rate setting is
incorrect.
BCU
RY
Match transmission baud rate setting between
BCU and relay.
Start bit, stop bit and parity settings of
data that BCU transmits to relay is
incorrect.
BCU
Go over the following settings by BCU. Relay
setting is fixed as following settings.
- Start bit: 1bit
- Stop bit: 1bit
- Parity setting: even
The PRTCL1 setting is incorrect. (The
model with PRTCL1
setting.)
RY
Change the PRTCL1 setting. Relation between
PRTCL1 setting and available transmission
protocol is referred to the following table.
RS485 port at the
back of the relay
PRTCL1
=HDLC
PRTCL1
=IEC
COM1 (CH1)
HDLC
IEC
COM2 (CH2)
IEC
―
RS485 or optical cable interconnection
is incorrect.
Cable
- Check the connection port.(CH1/CH2)
- Check the interconnection of RS485 A/B/COM
- Check the send and received interconnection of
optical cable.
The setting of converter is incorrect.
(RS485/optic conversion is executed
with the transmission channel, etc.)
Converter In the event of using G1IF2, change the DIPSW
setting in reference to INSTRUCTION MANUAL
(6F2S0794).
The relationship between logical “0/1” of
the signal and Sig.on/off is incorrect. (In
the event of using optical cable)
BCU
Check the following;
Logical0 : Sig.on
Logical1:Sig.off
Terminal resistor is not offered.
(Especially when RS485 cable is long.)
cable
Impose terminal resistor (150[ohms]) to both ends
of RS 485 cable.
Relay cannot receive the requirement
frame from BCU.
(The timing coordination of sending and
receiving switch control is irregular in
half-duplex communication.)
BCU
Check to secure the margin more than 15ms
between receiving the reply frame from the relay
and transmitting the next requirement frame on
BCU.
1 Communication
trouble
(
IEC103
communication is
not available.
)
The requirement frame from BCU and
the reply frame from relay contend.
(The sending and receiving timing
coordination is irregular in half-duplex
communication.)
BCU
Check to set the time-out of reply frame from the
relay.
Time-out setting: more than 100ms (acceptable
value of response time 50ms plus
margin)
Summary of Contents for GRL100-101A
Page 223: ... 222 6 F 2 S 0 8 3 5 ...
Page 228: ... 227 6 F 2 S 0 8 3 5 Appendix B Signal List ...
Page 256: ... 255 6 F 2 S 0 8 3 5 Appendix C Variable Timer List ...
Page 258: ... 257 6 F 2 S 0 8 3 5 Appendix D Binary Output Default Setting List ...
Page 269: ... 268 6 F 2 S 0 8 3 5 ...
Page 270: ... 269 6 F 2 S 0 8 3 5 Appendix E Details of Relay Menu ...
Page 279: ... 278 6 F 2 S 0 8 3 5 ...
Page 288: ... 287 6 F 2 S 0 8 3 5 Appendix G Typical External Connection ...
Page 326: ... 325 6 F 2 S 0 8 3 5 Appendix J Return Repair Form ...
Page 330: ... 329 6 F 2 S 0 8 3 5 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 331: ... 330 6 F 2 S 0 8 3 5 ...
Page 332: ... 331 6 F 2 S 0 8 3 5 Appendix K Technical Data ...
Page 343: ... 342 6 F 2 S 0 8 3 5 ...
Page 344: ... 343 6 F 2 S 0 8 3 5 Appendix L Symbols Used in Scheme Logic ...
Page 347: ... 346 6 F 2 S 0 8 3 5 ...
Page 348: ... 347 6 F 2 S 0 8 3 5 Appendix M Multi phase Autoreclose ...
Page 351: ... 350 6 F 2 S 0 8 3 5 ...
Page 352: ... 351 6 F 2 S 0 8 3 5 Appendix N Data Transmission Format ...
Page 358: ... 357 6 F 2 S 0 8 3 5 Appendix O Example of DIF and DIFG Setting ...
Page 364: ... 363 6 F 2 S 0 8 3 5 Appendix Q IEC60870 5 103 Interoperability ...
Page 377: ... 376 6 F 2 S 0 8 3 5 ...
Page 378: ... 377 6 F 2 S 0 8 3 5 Appendix R Failed Module Tracing and Replacement ...
Page 384: ... 383 6 F 2 S 0 8 3 5 Appendix S PLC Setting Sample ...
Page 386: ... 385 6 F 2 S 0 8 3 5 Appendix T Ordering ...
Page 392: ......