In case of two-terminal lines, enter the reactive and resistive component of the positive sequence
line impedance to the items 1X1 and 1R1 and line length to 1 Line. Press the enter key for each
entry.
Note:
The line impedance is input with the secondary value.
In case of three-terminal lines, enter the data on the first section from the local terminal to the
junction to the items expressed as 1
∗∗
, the data on the second section from the junction to the
remote terminal 1 to 2
∗∗
and the data on the third section from the junction to the remote
terminal 2 to 3
∗∗
.
•
Select 2 (= Phase impedances), then the following "Line data" screen is displayed.
In case of two-terminal lines, enter the reactive and resistive component of the self-impedances
and mutual-impedances of the line to the items expressed as 1X
∗∗
and 1R
∗∗
and line length to 1
Line. Press the ENTER key for each entry.
In case of three-terminal lines, enter the data on the first section from the local terminal to the
junction to 1
∗∗∗
, the data on the second section from the junction to the remote terminal 1 to
2
∗∗∗
and the data on the third section from the junction to the remote terminal 2 to 3
∗∗∗
.
•
Press the END key after completing the settings to return the display to the "Line
parameter" screen
Summary of Contents for GRL100-101A
Page 223: ... 222 6 F 2 S 0 8 3 5 ...
Page 228: ... 227 6 F 2 S 0 8 3 5 Appendix B Signal List ...
Page 256: ... 255 6 F 2 S 0 8 3 5 Appendix C Variable Timer List ...
Page 258: ... 257 6 F 2 S 0 8 3 5 Appendix D Binary Output Default Setting List ...
Page 269: ... 268 6 F 2 S 0 8 3 5 ...
Page 270: ... 269 6 F 2 S 0 8 3 5 Appendix E Details of Relay Menu ...
Page 279: ... 278 6 F 2 S 0 8 3 5 ...
Page 288: ... 287 6 F 2 S 0 8 3 5 Appendix G Typical External Connection ...
Page 326: ... 325 6 F 2 S 0 8 3 5 Appendix J Return Repair Form ...
Page 330: ... 329 6 F 2 S 0 8 3 5 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 331: ... 330 6 F 2 S 0 8 3 5 ...
Page 332: ... 331 6 F 2 S 0 8 3 5 Appendix K Technical Data ...
Page 343: ... 342 6 F 2 S 0 8 3 5 ...
Page 344: ... 343 6 F 2 S 0 8 3 5 Appendix L Symbols Used in Scheme Logic ...
Page 347: ... 346 6 F 2 S 0 8 3 5 ...
Page 348: ... 347 6 F 2 S 0 8 3 5 Appendix M Multi phase Autoreclose ...
Page 351: ... 350 6 F 2 S 0 8 3 5 ...
Page 352: ... 351 6 F 2 S 0 8 3 5 Appendix N Data Transmission Format ...
Page 358: ... 357 6 F 2 S 0 8 3 5 Appendix O Example of DIF and DIFG Setting ...
Page 364: ... 363 6 F 2 S 0 8 3 5 Appendix Q IEC60870 5 103 Interoperability ...
Page 377: ... 376 6 F 2 S 0 8 3 5 ...
Page 378: ... 377 6 F 2 S 0 8 3 5 Appendix R Failed Module Tracing and Replacement ...
Page 384: ... 383 6 F 2 S 0 8 3 5 Appendix S PLC Setting Sample ...
Page 386: ... 385 6 F 2 S 0 8 3 5 Appendix T Ordering ...
Page 392: ......