PLC setting sample for autoreclosing (UARCSW application)
If the follower Terminal is reclosed after checking the leader Terminal reclosed in the autoreclose
mode “SPAR”, the leader Terminal is assigned to the signal number 1 with signal name
“CONSTANT_1” and the follower Terminal assigned to the signal number 498 with signal name
“3PLL” as shown in Figure S-1.
Single-phase trip
+
[ARC-M]
"SPAR", "SPAR & TPAR"
&
≥
1
No-Link & Single-phase trip
+
[ARC-M]
"MPAR2", "MPAR3"
&
&
0.01-10s
t 0
TSPR1
SPR.L-REQ
1824
CONSTANT 1
&
≥
1
0.1 - 10s
TW1
ARC
MSARC
ARC
(For Leader CB)
Leader Terminal
Single-phase trip
+
[ARC-M]
"SPAR", "SPAR & TPAR"
&
≥
1
No-Link & Single-phase trip
+
[ARC-M]
"MPAR2", "MPAR3"
&
&
0.01-10s
t 0
TSPR1
SPR.L-REQ
1824
3PLL
&
≥
1
0.1 - 10s
TW1
ARC
MSARC
ARC
(For Leader CB)
Follower Terminal
Figure S-1
In this case, the reclosing condition of [SPR.L-REQ] is the difference between the leader Terminal
and the follower Terminal. If the same setting is required for the reclosing condition of
[SPR.L-REQ], set the PLC using the [UARCSW] described in 2.10.2 as follows:
"P1"
&
≥
1
+
[UARCSW]
"3PLL"
&
0.01-10s
t 0
TSPR1
SPR.L-REQ
1824
&
≥
1
0.1 - 10s
TW1
ARC
MSARC
ARC
(For Leader CB)
"P2"
Figure S-2
The reclose condition can be changed by the position of [UARCSW].
[UARCSW] = P1: (No condition for reclosing)
[UARCSW] = P2: 3PLL (Three phase live line condition for reclosing)
The [UARCSW] is effective when the reclosing condition of PLC setting has the difference
between the leader Terminal and the follower Terminal.
Summary of Contents for GRL100-101A
Page 223: ... 222 6 F 2 S 0 8 3 5 ...
Page 228: ... 227 6 F 2 S 0 8 3 5 Appendix B Signal List ...
Page 256: ... 255 6 F 2 S 0 8 3 5 Appendix C Variable Timer List ...
Page 258: ... 257 6 F 2 S 0 8 3 5 Appendix D Binary Output Default Setting List ...
Page 269: ... 268 6 F 2 S 0 8 3 5 ...
Page 270: ... 269 6 F 2 S 0 8 3 5 Appendix E Details of Relay Menu ...
Page 279: ... 278 6 F 2 S 0 8 3 5 ...
Page 288: ... 287 6 F 2 S 0 8 3 5 Appendix G Typical External Connection ...
Page 326: ... 325 6 F 2 S 0 8 3 5 Appendix J Return Repair Form ...
Page 330: ... 329 6 F 2 S 0 8 3 5 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 331: ... 330 6 F 2 S 0 8 3 5 ...
Page 332: ... 331 6 F 2 S 0 8 3 5 Appendix K Technical Data ...
Page 343: ... 342 6 F 2 S 0 8 3 5 ...
Page 344: ... 343 6 F 2 S 0 8 3 5 Appendix L Symbols Used in Scheme Logic ...
Page 347: ... 346 6 F 2 S 0 8 3 5 ...
Page 348: ... 347 6 F 2 S 0 8 3 5 Appendix M Multi phase Autoreclose ...
Page 351: ... 350 6 F 2 S 0 8 3 5 ...
Page 352: ... 351 6 F 2 S 0 8 3 5 Appendix N Data Transmission Format ...
Page 358: ... 357 6 F 2 S 0 8 3 5 Appendix O Example of DIF and DIFG Setting ...
Page 364: ... 363 6 F 2 S 0 8 3 5 Appendix Q IEC60870 5 103 Interoperability ...
Page 377: ... 376 6 F 2 S 0 8 3 5 ...
Page 378: ... 377 6 F 2 S 0 8 3 5 Appendix R Failed Module Tracing and Replacement ...
Page 384: ... 383 6 F 2 S 0 8 3 5 Appendix S PLC Setting Sample ...
Page 386: ... 385 6 F 2 S 0 8 3 5 Appendix T Ordering ...
Page 392: ......