Monobloc Outdoor Unit Service Manual
73
If there is a problem of readiness af alarm by remote controller or service tools, it is possible in the second time to
check error from the LED D800 to D804 on MCC-1599 board. By lighting LED D800 to D804, past or current alarm
can be identified (refer to tables below)
How to read the LED diagnostic:
a) When all Dip switch of SW 803 are OFF, the current status of error which is displayed (current alarm)
b) When only DIP switch ‘1’ of SW803 is turned ON, the last error generated on unit is displayed (past error)
c) If there is an error, any LED D800 to D804 goes ON (Display 1)
d) When pushing the pushdown button switch SW800 for approx.1 second, the display is exchanged to Display 2
e) When pushing SW800 again or after 2 minutes, the status returns to Display 1.
Summary of Contents for Estia RUA-CP1701H
Page 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Page 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Page 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Page 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Page 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Page 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Page 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Page 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Page 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Page 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Page 162: ......
Page 163: ......
Page 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...