Monobloc Outdoor Unit Service Manual
110
10.1.3.4. Pump Status Table
Access type: Read-only (force is possible)
TABLE NAME: PMP_STAT, PIC Table Type: 11H, instance 4
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
81
pmp_ovr
-1 to 16
-
-
Pump Override
1
105
FLOW_SW
Open / Close
-
-
Flow Switch Status
82
flow_err
Normal / Alarm
-
-
Water Flow Failure
83
dtstp
xx.x
-
^C
Current DeltaT Setpoint
84
delta_t
±xx.x
-
^C
Water Delta Temperature
85
PMP
0 to 100
-
%
Water Pump Speed
2
88
ADD_PMP
Off / On
-
-
Additional Pump
3
1. Pump override
-1 = Pump Control disabled
0 = No override
1 = Compressor Still Running
2 = Flow Switch Failure
3 = Pump Stopping Delay
4 = Anti-Sticking
5 = Low OAT
6 = Very Low OAT
7 = Defrost Active, run the pump at maximum speed
8 = Boiler Active (and compressor is stopped), stop the
pump
9 = DHW Active
10 = Header/Follower active
11 = Water Sampling
12 = Purge Mode
13 = Freeze protection alarm #50 or #52, run the pump
14 = Pump stopped due to Compressor or Inverter failure
15 = DHW Valve moving, run the pump
16 = Water Control Point Reached, control variable speed
pump on CTRL_PNT
2. Water pump speed
For Fixed Speed Pump:
0% = Stopped 100% = Running
3. Additional pump output
The additional pump installed in the heating loop.
10.1.3.5. Backup Status Table
Access type: Read-only (force is possible)
TABLE NAME: BCK_STAT, PIC Table Type: 11H, instance 5
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
91
back_ovr
-1 to 100
-
-
Backup Override
1
92
back_flg
No / Yes
-
-
Backup Authorized flag
93
warmtime
0 to 1800
-
sec
Booster Warm Up timer
94
BACK_CAP
0 to 100
-
%
Backup Capacity
30
BOILER
Off / On
-
-
Boiler
31
EHS
0 to 3
-
-
Electrical Heat Stages
1. Backup override
-1 = Backup disabled
0 = No override
1 = Backup running due to Heat Pump low capacity
2 = Backup running as booster heating
3 = Backup running during Defrost
4 = Backup running due to Heat Pump failure
5 = Backup running due to low OAT
10 = Off-peak active (do not allow electric backup)
11 = Loadshed active (do not allow electric backup)
12 = Backup stopped due to DHW Mode
13 = Capacity Limit (do not allow electric backup)
14 = Summer Mode (do not allow backup)
50 = Backup not allowed
51 = No Heating Demand
100 = Backup failed
Summary of Contents for Estia RUA-CP1701H
Page 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Page 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Page 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Page 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Page 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Page 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Page 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Page 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Page 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Page 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Page 162: ......
Page 163: ......
Page 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...