Monobloc Outdoor Unit Service Manual
48
Related parameters for cooling climatic curve control (predefined and custom):
Par.No
Description
Range
Default
408
Cool sleep offset – (cwunooff): (K)
0.0 ~ 10.0
0.0
409
Cool away offset – (cwecooff): (K)
0.0 ~ 10.0
0.0
413
Cool curve min. set-point offset – (ccurvoff): (K)
-5.0 ~ 5.0
0.0
586
Cool clim curve select – (cl_curv)
-1 ~ 2
-1
587
Cool minimum OAT – (cl_min_a): (°C)
0.0 ~ 30.0
20.0
588
Cool maximum OAT – (cl_min_a): (°C)
24.0 ~ 46.0
35.0
589
Cool min. water set-point – (cl_min_w): (°C)
5.0 ~ 20.0
10.0
590
Cool max. water set-point – (cl_min_w): (°C)
5.0 ~ 20.0
18.0
ii)
Heating mode:
Auto curve control, for heating mode operation, can be enabled by setting the Heat Clim Curve Select parameter
[P581] as shown below:
Par.No
Setting
Function
581
-1
No curve (fixed water temperature)
0
Custom climatic curve
1
Heating climatic curve 1
12
Heating climatic curve 12
•
Custom climatic curve:
If the heating climatic curve [ht_curv] is configured to "0", the water set-point will be calculated according to the
custom heating climatic curve. This custom heating climatic curve can be defined using the following parameters in
the CLIMCURV table:
Parameters
Description
Default
Minimum Maximum
ht_min_a
582
Custom Minimum OAT
-7.0°C
-30°C
10°C
ht_max_a
583
Custom Maximum OAT
20.0°C
10°C
30°C
ht_min_w
584
Custom Minimum Water Temp
20.0°C
20°C
40°C
ht_max_w
585
Custom Maximum Water Temp
38.0°C
30°C
60°C
•
If OAT is invalid, the Water Setpoint is equal to the Custom Max. Water Temp.
•
If OAT is above the current Maximum OAT threshold, the Water Setpoint is equal to the Custom Min. Water
Temp.
If Min. OAT is greater or equal to Max. OAT threshold, the Water Setpoint is equal to the custom Max. Water Temp.
Summary of Contents for Estia RUA-CP1701H
Page 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Page 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Page 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Page 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Page 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Page 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Page 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Page 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Page 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Page 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Page 162: ......
Page 163: ......
Page 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...