Monobloc Outdoor Unit Service Manual
88
9.4.1.16.
Alarm 61 – Fan error
Alarm 61
Fan error
9.4.1.17. Alarm 62 – Compressor inverter short circuit protection
Alarm 62
Compressor inverter short circuit protection
9.4.1.18. Alarm 63 – Compressor motor position detection error
Alarm 63
Compressor motor position detection error
Are fan connectors connected
correctly?
YES
Check wiring (refer to wiring diagram)
NO
Is pipe crushed on refrigerant
circuit?
NO
YES
Check operation of inverter box
Defective fan motor - replace
Replace fan motor
YES
Is there a problem on connection
of compressor lead or reactor?
(check referring to wiring
diagram)
NO
Check wiring (refer to wiring diagram)
NO
Is pipe crushed on refrigerant
circuit?
NO
Defective fan motor - replace
Replace fan motor
YES
Check correct operation of inverter box
Defect
Replace
Summary of Contents for Estia RUA-CP1701H
Page 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Page 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Page 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Page 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Page 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Page 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Page 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Page 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Page 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Page 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Page 162: ......
Page 163: ......
Page 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...