Monobloc Outdoor Unit Service Manual
85
9.4.1.12.
Alarm 33 – Inverter high pressure release failure
Electrical connection
Alarm 33
Inverter high pressure release failure
CN690 on MCC-1599
Does fan normally operate?
Elimination of blocking element
NO
YES
Is there no fan breakage or coming off?
Repair defective position:
connection of connectors / fan
board / fan motor / wiring
Is there any element which
blocks air heat exchanger?
- Clogging of heat exchanger
- Bypass in heat exchanger
YES
NO
Overcharge of refrigerant /
clogging / pipe breakage /
abnormal load
Cooling operation
Doesn’t high pressure switch
operate?
Check parts – if defective, replace
YES
Is circuit wiring normal?
Are parts of high pressure switch
normal?
NO
YES
Check inverter box – if defective,
replace
YES
Reset the power supply and then
do a trial operation according to
the season
NO
NO
Wiring check, correct
Summary of Contents for Estia RUA-CP1701H
Page 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Page 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Page 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Page 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Page 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Page 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Page 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Page 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Page 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Page 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Page 162: ......
Page 163: ......
Page 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...